Siemens LOGO! Siemens LOGO! Integration Guide

Read and write Siemens LOGO! 8 logic modules by LOGO! address. The LOGO! connector speaks S7 (ISO-on-TCP, port 102) and reaches the module through a connection set up in LOGO!Soft Comfort, by its TSAP pair.

Overview​

The LOGO! connector provides:

  • LOGO! addresses: read I, Q, M, AI, AQ, AM, NI, NQ, NAI, NAQ and the V memory as the LOGO! names them (I1, Q3, AI2, NI5, VW10)
  • Types that follow the address: bits as booleans, analog values as 16-bit integers, V bytes, words and double words
  • Many points in the fewest reads: every area is a slice of one memory, so neighbouring points share a read
  • Writes to network inputs and V memory: the only addresses a LOGO! program does not rewrite every cycle
Supported modules

LOGO! 8 base modules with Ethernet: 0BA8, 8.FS4 and 8.3. Older modules (0BA7 and earlier) use a different memory layout and are not supported.

Connection Configuration​

A LOGO! accepts an S7 client only through a connection configured in LOGO!Soft Comfort:

  1. Open Tools → Ethernet Connections (on a LOGO! 8, right-click Ethernet Connections → Add connection).
  2. Add a server connection (S7). Note its Local Properties (Server) TSAP, e.g. 02.00, and its Remote Properties (Client) TSAP, e.g. 10.00.
  3. Leave Only read access unticked if MaestroHub should write network inputs or V memory.
  4. Download the program to the LOGO!.

The TSAPs cross: the connection's local TSAP is the LOGO!'s own, which MaestroHub calls the Remote TSAP; the connection's remote TSAP is MaestroHub's, its Local TSAP.

Creating a LOGO! Connection​

Navigate to Connections → New Connection → Siemens LOGO!.

FieldDefaultDescription
Address—The LOGO!'s IP address or host name (required)
Port102S7 port. A LOGO! serves 102.
Local TSAP10.00MaestroHub's TSAP: the Remote TSAP of the LOGO!Soft connection
Remote TSAP02.00The LOGO!'s TSAP: the Local TSAP of the LOGO!Soft connection
Timeout5sMaximum time to connect, and to wait for each answer

A TSAP is two hex bytes separated by a dot. The defaults are the ones the previous LOGO! driver used, so a module already set up for it connects unchanged.

Testing the Connection​

Test Connection opens the S7 connection with the TSAPs and reads one byte of the LOGO!'s memory. A LOGO! that refuses the connection usually has no server connection with these TSAPs, or a different program was downloaded.

LOGO! Addresses​

Every LOGO! address is a slice of the module's variable memory (VM). The type follows from the address.

AddressWhat it isRangeTypeWritten
IDigital inputsI1–I64BITNo
QDigital outputsQ1–Q64BITNo
MFlagsM1–M112BITNo
AIAnalog inputsAI1–AI16INTNo
AQAnalog outputsAQ1–AQ16INTNo
AMAnalog flagsAM1–AM64INTNo
NINetwork inputsNI1–NI128BITYes
NAINetwork analog inputsNAI1–NAI64INTYes
NQNetwork outputsNQ1–NQ128BITNo
NAQNetwork analog outputsNAQ1–NAQ32INTNo
VV memory bitV0.0–V850.7BITYes
VBV memory byteVB0–VB850BYTE (0–255)Yes
VWV memory wordVW0–VW849INT (−32768–32767)Yes
VDV memory double wordVD0–VD847DINTYes
Why most areas are not written

The LOGO! program rewrites its inputs, outputs, flags and analog values on every cycle, so a value written there reverts before it does anything. To command a LOGO!, use a network input in the program (an NI or NAI block) or have the program read a V memory address, and write that.

Function Builder​

Read Points (logo.read)​

Read a set of named points, each by LOGO! address, in the fewest reads.

FieldRequiredDescription
PointsYesOne or more {name, address}: the name is the key in the result, the address a LOGO! address

Example: pump = Q1, level = AI2, setpoint = VW10 returns { "pump": true, "level": 512, "setpoint": 750 } under values.

A point name may not repeat, and an address a LOGO! 8 does not have (such as Q65) is refused when the function is saved.

Write Point (logo.write)​

Write one value to a network input or V memory address.

FieldRequiredDescription
AddressYesNI1–NI128, NAI1–NAI64, or V memory (V10.3, VB10, VW10, VD10). Supports ((paramName)).
ValueYestrue/false (also on/off, 1/0) for a bit, a whole number otherwise. Supports ((paramName)).

A single bit is written by reading its byte, setting the bit and writing the byte back. Network inputs are written only by clients, so this is safe there; if the program also writes other bits of the same V byte, a write can race with it.

Testing Functions​

Use Test Function on the function form to run a read or write against the live LOGO! before saving it.

Pipeline Integration​

Each operation has its own node: LOGO! Read and LOGO! Write. See Siemens LOGO! Nodes for their parameters and results.

Troubleshooting​

SymptomPossible causeSolution
Test Connection fails with a connection errorNo server connection with these TSAPs on the LOGO!, or the address is wrongCheck the LOGO!Soft connection's TSAPs (they cross) and that the program with the connection was downloaded
the LOGO! refused the request on a writeThe LOGO!Soft connection is set to Only read accessUntick it and download the program again
… is set by the LOGO! program every cycleA write to I, Q, M or an analog valueWrite a network input (NI, NAI) or a V address the program reads
a LOGO! 8 has Q1-Q64 (or similar)An address the module does not haveUse an address in the range shown
A V value reads as garbageThe program keeps it at another V address, or as another widthCheck the address and width in LOGO!Soft (VB, VW or VD)