IEC 61850 Nodes
Read and write protection relays, bay controllers and station gateways over MMS from a pipeline.
- Status
- Beta
- Reads
- Browse Model · Read Attributes · Read Data Set
- Writes
- Write Attribute (checked against the IED's type first)
Use IEC 61850 IEDs in pipelines. Each function authored on an IEC 61850 connection is available as a matching node in the Pipeline Designer.
For connection setup, references and functional constraints, see the IEC 61850 connection guide.
For reports as a pipeline trigger, see the IEC 61850 Trigger.
Configuration Quick Reference
| Field | What you choose | Details |
|---|---|---|
| Parameters | Connection, Function, Function Parameters, Timeout Override | Select the IEC 61850 connection, pick a function, bind parameters with expression support, and optionally override the timeout. |
| Settings | Description, Timeout (seconds), Retry on Timeout, Retry on Fail, On Error | Node description, maximum execution time, retry behaviour and error strategy. All execution settings default to pipeline-level values. |
Every node's _metadata carries _metadata.method (the function's operation, such as iec61850.read), _metadata.protocol (iec61850) and _metadata.connectionId.
IEC 61850 Browse Model Node
Supported Function Types:
| Node | Function | Purpose | Common Use Cases |
|---|---|---|---|
IEC 61850 Browse Model (connected.iec61850.browse) | iec61850.browse | One level of the IED's model | Discover references; list the data sets and report control blocks of a logical device |
Output Structure
{
"result": {
"reference": "IED1LD0/MMXU1",
"kind": "logicalNode",
"count": 1,
"children": [
{ "name": "TotW", "reference": "IED1LD0/MMXU1.TotW", "kind": "dataObject", "fcs": ["MX"], "type": null }
],
"dataSets": [],
"reportControlBlocks": []
}
}
| Key | Meaning |
|---|---|
result.reference | The reference browsed; empty for the server |
result.kind | What was browsed: server, logicalDevice, logicalNode, dataObject or component |
result.children | One entry per child: name, reference, kind (logicalDevice, logicalNode, dataObject, component or dataAttribute), fcs (the functional constraints it exists under) and type (for an attribute) |
result.count | How many children were listed |
result.dataSets | The data sets of a browsed logical device; empty otherwise |
result.reportControlBlocks | The report control blocks of a browsed logical device, each {reference, buffered}; empty otherwise |


IEC 61850 Read Attributes node
IEC 61850 Read Attributes Node
Supported Function Types:
| Node | Function | Purpose | Common Use Cases |
|---|---|---|---|
IEC 61850 Read Attributes (connected.iec61850.read) | iec61850.read | The current value of data attributes or whole data objects | Measurements and positions on a schedule; settings audit |
Node Configuration
| Parameter | Type | Required | Description |
|---|---|---|---|
| Connection | Selection | Yes | IEC 61850 connection profile to use |
| Function | Selection | Yes | An iec61850.read function from the selected connection |
| Function Parameters | Dynamic | Varies | The reference list can be a ((parameter)). See Read Attributes. |
| Timeout Override | Number (seconds) | No | Override the default function timeout |
Output Structure
{
"result": {
"count": 2,
"failed": 1,
"values": [
{
"reference": "IED1LD0/MMXU1.TotW", "fc": "MX", "status": "ok",
"value": 231.5, "valuePath": "mag.f", "type": "FLOAT32",
"attributes": { "mag": { "f": 231.5 }, "q": { "validity": "good" }, "t": "2026-11-20T10:14:03.24Z" },
"quality": "good", "flags": { "validity": "good", "oldData": false },
"sourceTimestamp": "2026-11-20T10:14:03.24Z",
"detail": { "timeQuality": { "clockFailure": false, "clockNotSynchronized": false, "leapSecondKnown": true, "timeAccuracy": 10 } }
},
{ "reference": "IED1LD0/MMXU1.Hz", "fc": "MX", "status": "error", "error": "object-non-existent", "errorCode": 10 }
]
}
}
| Key | Meaning |
|---|---|
result.values | One entry per reference, in the order given: status ok with value, valuePath, type, attributes, quality, flags, sourceTimestamp and detail, or status error with the IED's error and errorCode |
result.count | How many references were read |
result.failed | How many of them the IED refused |
Read a value with $node["Read Feeder"].result.values[0].value. A refused reference never carries a value.
IEC 61850 Read Data Set Node
Supported Function Types:
| Node | Function | Purpose | Common Use Cases |
|---|---|---|---|
IEC 61850 Read Data Set (connected.iec61850.readDataSet) | iec61850.readDataSet | Every member of a data set | A snapshot of the same values a report carries |
Output Structure
{
"result": {
"dataSet": "IED1LD0/LLN0.Measurements",
"count": 1,
"failed": 0,
"members": [
{ "reference": "IED1LD0/MMXU1.TotW.mag.f", "fc": "MX", "status": "ok", "value": 231.5, "valuePath": "", "type": "FLOAT32", "attributes": null, "quality": null, "flags": null, "sourceTimestamp": null, "detail": {} }
]
}
}
| Key | Meaning |
|---|---|
result.dataSet | The data set read |
result.members | One entry per member, in data set order, shaped like a read's values |
result.count | How many members the data set has |
result.failed | How many members the IED refused |


IEC 61850 Write Attribute node
IEC 61850 Write Attribute Node
Supported Function Types:
| Node | Function | Purpose | Common Use Cases |
|---|---|---|---|
IEC 61850 Write Attribute (connected.iec61850.write) | iec61850.write | Write one data attribute in the type the IED declares | Set-points, settings, substitution values, descriptions |
The value is encoded in the attribute's type, read from the IED first; a value that does not fit is refused before anything is written. A write is never buffered and never runs on a late (replayed) input. A write whose answer did not arrive is reported as outcome unknown: the IED may already have written it. Writing the same value again is harmless, so Retry on Fail, when it is on, may send it again.
Output Structure
{
"result": { "reference": "IED1LD0/DRCC1.WMaxSpt.setMag.f", "fc": "SP", "type": "FLOAT32", "value": 12.5 }
}
| Key | Meaning |
|---|---|
result.reference | The attribute written |
result.fc | The functional constraint written |
result.type | The attribute's type, as the IED declares it |
result.value | The value the IED accepted, in that type |
Settings Tab
All IEC 61850 node types share the same Settings tab:
| Setting | Type | Default | Description |
|---|---|---|---|
| Description | Text | - | Optional description displayed on the node |
| Timeout (seconds) | Number | Pipeline default | Maximum time the node may run before timing out |
| Retry on Timeout | Toggle | Pipeline default | Automatically retry the node if it times out |
| Retry on Fail | Toggle | Pipeline default | Automatically retry the node if it fails |
| On Error | Selection | Pipeline default | Error strategy: Pipeline Default (the pipeline's Error Handling setting), Stop Pipeline or Continue Execution |
When left at their defaults, these settings inherit from the pipeline-level execution configuration.
Errors
| Error | Meaning | Retried by the node settings? |
|---|---|---|
reference "…": add its functional constraint | A reference without [FC]; nothing was sent | No |
value "…": INT16 takes a whole number from -32768 to 32767 | The value does not fit the attribute's type; nothing was written | No |
object-access-denied | The IED refused the write | No |
the write may have reached the IED, but its answer did not arrive | The outcome of a write is unknown | Retry on Fail, when on (the same value again) |
not connected | The connection is down; nothing was sent | Read nodes, as configured |