IEC 61850 Nodes

Read and write protection relays, bay controllers and station gateways over MMS from a pipeline.

Status
Beta
Reads
Browse Model · Read Attributes · Read Data Set
Writes
Write Attribute (checked against the IED's type first)

Use IEC 61850 IEDs in pipelines. Each function authored on an IEC 61850 connection is available as a matching node in the Pipeline Designer.

For connection setup, references and functional constraints, see the IEC 61850 connection guide.

For reports as a pipeline trigger, see the IEC 61850 Trigger.

Configuration Quick Reference​

FieldWhat you chooseDetails
ParametersConnection, Function, Function Parameters, Timeout OverrideSelect the IEC 61850 connection, pick a function, bind parameters with expression support, and optionally override the timeout.
SettingsDescription, Timeout (seconds), Retry on Timeout, Retry on Fail, On ErrorNode description, maximum execution time, retry behaviour and error strategy. All execution settings default to pipeline-level values.

Every node's _metadata carries _metadata.method (the function's operation, such as iec61850.read), _metadata.protocol (iec61850) and _metadata.connectionId.


IEC 61850 Browse Model Node​

Supported Function Types:

NodeFunctionPurposeCommon Use Cases
IEC 61850 Browse Model (connected.iec61850.browse)iec61850.browseOne level of the IED's modelDiscover references; list the data sets and report control blocks of a logical device

Output Structure​

{
"result": {
"reference": "IED1LD0/MMXU1",
"kind": "logicalNode",
"count": 1,
"children": [
{ "name": "TotW", "reference": "IED1LD0/MMXU1.TotW", "kind": "dataObject", "fcs": ["MX"], "type": null }
],
"dataSets": [],
"reportControlBlocks": []
}
}
KeyMeaning
result.referenceThe reference browsed; empty for the server
result.kindWhat was browsed: server, logicalDevice, logicalNode, dataObject or component
result.childrenOne entry per child: name, reference, kind (logicalDevice, logicalNode, dataObject, component or dataAttribute), fcs (the functional constraints it exists under) and type (for an attribute)
result.countHow many children were listed
result.dataSetsThe data sets of a browsed logical device; empty otherwise
result.reportControlBlocksThe report control blocks of a browsed logical device, each {reference, buffered}; empty otherwise

IEC 61850 Read Attributes nodeIEC 61850 Read Attributes node

IEC 61850 Read Attributes node

IEC 61850 Read Attributes Node​

Supported Function Types:

NodeFunctionPurposeCommon Use Cases
IEC 61850 Read Attributes (connected.iec61850.read)iec61850.readThe current value of data attributes or whole data objectsMeasurements and positions on a schedule; settings audit

Node Configuration​

ParameterTypeRequiredDescription
ConnectionSelectionYesIEC 61850 connection profile to use
FunctionSelectionYesAn iec61850.read function from the selected connection
Function ParametersDynamicVariesThe reference list can be a ((parameter)). See Read Attributes.
Timeout OverrideNumber (seconds)NoOverride the default function timeout

Output Structure​

{
"result": {
"count": 2,
"failed": 1,
"values": [
{
"reference": "IED1LD0/MMXU1.TotW", "fc": "MX", "status": "ok",
"value": 231.5, "valuePath": "mag.f", "type": "FLOAT32",
"attributes": { "mag": { "f": 231.5 }, "q": { "validity": "good" }, "t": "2026-11-20T10:14:03.24Z" },
"quality": "good", "flags": { "validity": "good", "oldData": false },
"sourceTimestamp": "2026-11-20T10:14:03.24Z",
"detail": { "timeQuality": { "clockFailure": false, "clockNotSynchronized": false, "leapSecondKnown": true, "timeAccuracy": 10 } }
},
{ "reference": "IED1LD0/MMXU1.Hz", "fc": "MX", "status": "error", "error": "object-non-existent", "errorCode": 10 }
]
}
}
KeyMeaning
result.valuesOne entry per reference, in the order given: status ok with value, valuePath, type, attributes, quality, flags, sourceTimestamp and detail, or status error with the IED's error and errorCode
result.countHow many references were read
result.failedHow many of them the IED refused

Read a value with $node["Read Feeder"].result.values[0].value. A refused reference never carries a value.


IEC 61850 Read Data Set Node​

Supported Function Types:

NodeFunctionPurposeCommon Use Cases
IEC 61850 Read Data Set (connected.iec61850.readDataSet)iec61850.readDataSetEvery member of a data setA snapshot of the same values a report carries

Output Structure​

{
"result": {
"dataSet": "IED1LD0/LLN0.Measurements",
"count": 1,
"failed": 0,
"members": [
{ "reference": "IED1LD0/MMXU1.TotW.mag.f", "fc": "MX", "status": "ok", "value": 231.5, "valuePath": "", "type": "FLOAT32", "attributes": null, "quality": null, "flags": null, "sourceTimestamp": null, "detail": {} }
]
}
}
KeyMeaning
result.dataSetThe data set read
result.membersOne entry per member, in data set order, shaped like a read's values
result.countHow many members the data set has
result.failedHow many members the IED refused

IEC 61850 Write Attribute nodeIEC 61850 Write Attribute node

IEC 61850 Write Attribute node

IEC 61850 Write Attribute Node​

Supported Function Types:

NodeFunctionPurposeCommon Use Cases
IEC 61850 Write Attribute (connected.iec61850.write)iec61850.writeWrite one data attribute in the type the IED declaresSet-points, settings, substitution values, descriptions

The value is encoded in the attribute's type, read from the IED first; a value that does not fit is refused before anything is written. A write is never buffered and never runs on a late (replayed) input. A write whose answer did not arrive is reported as outcome unknown: the IED may already have written it. Writing the same value again is harmless, so Retry on Fail, when it is on, may send it again.

Output Structure​

{
"result": { "reference": "IED1LD0/DRCC1.WMaxSpt.setMag.f", "fc": "SP", "type": "FLOAT32", "value": 12.5 }
}
KeyMeaning
result.referenceThe attribute written
result.fcThe functional constraint written
result.typeThe attribute's type, as the IED declares it
result.valueThe value the IED accepted, in that type

Settings Tab​

All IEC 61850 node types share the same Settings tab:

SettingTypeDefaultDescription
DescriptionText-Optional description displayed on the node
Timeout (seconds)NumberPipeline defaultMaximum time the node may run before timing out
Retry on TimeoutTogglePipeline defaultAutomatically retry the node if it times out
Retry on FailTogglePipeline defaultAutomatically retry the node if it fails
On ErrorSelectionPipeline defaultError strategy: Pipeline Default (the pipeline's Error Handling setting), Stop Pipeline or Continue Execution

When left at their defaults, these settings inherit from the pipeline-level execution configuration.

Errors​

ErrorMeaningRetried by the node settings?
reference "…": add its functional constraintA reference without [FC]; nothing was sentNo
value "…": INT16 takes a whole number from -32768 to 32767The value does not fit the attribute's type; nothing was writtenNo
object-access-deniedThe IED refused the writeNo
the write may have reached the IED, but its answer did not arriveThe outcome of a write is unknownRetry on Fail, when on (the same value again)
not connectedThe connection is down; nothing was sentRead nodes, as configured