IEC 61850 trigger node
IEC 61850 Trigger Node
Start a pipeline each time an IED reports a data set member, with its value, IEC quality, device timestamp and why it was reported.
- Starts on
- Data change · quality change · update · integrity · general interrogation
- Function
- Receive Reports
- Output
- One event per reported data set member
- Dedup
- None: every report starts a run
Overview
The IEC 61850 Trigger Node starts a pipeline for each data set member an IEC 61850 IED reports through a report control block (RCB). Unlike the Read Attributes node, which reads values inside an already-running pipeline, the trigger starts a new execution for every reported member, enabling event-driven automation.
An RCB sends a report when a member of its data set changes (data or quality), is updated, at every integrity period, and in answer to a general interrogation, as its trigger options say. Buffered RCBs (BRCB) keep reporting into a buffer while MaestroHub is not connected; unbuffered RCBs (URCB) do not.
Core Functionality
What It Does
1. Event-Driven Pipeline Execution Each report is split into its members; each member starts one run.
2. The RCB Is Set Up for You When the pipeline is enabled, and after every reconnect, the Receive Reports function enables its RCB on the IED: it reserves an unbuffered RCB, sets the trigger options and integrity period when the function sets them, resumes a buffered RCB after the last entry received, enables it, and asks for a general interrogation. See Receive Reports.
3. Automatic Subscription Lifecycle The subscription is created when the pipeline becomes enabled and removed when it is disabled; removing it disables the RCB on the IED, so another client can take it.
4. No Deduplication Every event carries the time MaestroHub received the report, so two reports of the same value are two events. Each one starts a run.
Reconnection Handling
When the association with the IED ends, the trigger fires once with quality: bad (see _metadata below), and the IED disables the RCB. When the connection is back, MaestroHub enables the RCB again: a buffered RCB resumes after the last entry received, so reports the IED buffered meanwhile arrive late but complete; an unbuffered RCB starts from now, and the general interrogation (when on) brings every member's current value.
Configuration Options
Basic Information
| Field | Type | Description |
|---|---|---|
| Node Label | String (Required) | Display name for the node on the pipeline canvas. Must be non-empty (trimmed). |
| Description | String (Optional) | Explains what this trigger initiates. |
Configuration
| Parameter | Type | Default | Required | Description |
|---|---|---|---|---|
| Connection | Connection ID | "" | Yes | The IEC 61850 connection profile to receive reports from. Filtered to IEC 61850 connections only. |
| Receive Reports Function | Function ID | "" | Yes | The function naming the RCB. Filtered to iec61850.reports functions on the selected connection. |
| Enabled | Boolean | true | No | When disabled, the subscription is not created even if the pipeline is enabled. |
An RCB instance is enabled for one client and one function. Two Receive Reports functions on the same connection cannot name the same RCB, nor two RCBs whose reports cannot be told apart (the same report ID and data set, as the instances …01, …02 of one RCB usually have). To get the same reports into two pipelines, use the same Receive Reports function in both.
Sample Payload
The Parameters tab also holds a Sample Payload editor and a Sample Quality picker. When you run the node with Test Node in Sandbox mode, the trigger emits the sample payload as result instead of waiting for a real report.
Settings
| Setting | Options | Default | Description |
|---|---|---|---|
| On Error | Pipeline Default / Stop Pipeline / Continue Execution | Pipeline Default | Behavior when the node fails. |
Output Data Structure
Output Format
{
"result": {
"reference": "IED1LD0/MMXU1.TotW",
"fc": "MX",
"value": 231.5,
"valuePath": "mag.f",
"type": "FLOAT32",
"attributes": { "mag": { "f": 231.5 }, "q": { "validity": "good" }, "t": "2026-11-20T10:14:03.24Z" },
"quality": "good",
"flags": { "validity": "good", "overflow": false, "outOfRange": false, "badReference": false, "oscillatory": false, "failure": false, "oldData": false, "inconsistent": false, "inaccurate": false, "substituted": false, "test": false, "operatorBlocked": false },
"reason": "dataChange",
"report": { "rcb": "IED1LD0/LLN0.BR.brcbMeas01", "rptId": "Meas", "dataSet": "IED1LD0/LLN0.Measurements", "seqNum": 17, "entryId": "0000000000000011", "confRev": 1, "bufferOverflow": false, "timestamp": "2026-11-20T10:14:03.25Z" },
"detail": { "timeQuality": { "clockFailure": false, "clockNotSynchronized": false, "leapSecondKnown": true, "timeAccuracy": 10 } },
"sourceTimestamp": "2026-11-20T10:14:03.24Z",
"serverTimestamp": "2026-11-20T10:14:03.31Z"
},
"_metadata": {
"type": "iec61850_trigger",
"protocol": "iec61850",
"rcb": "IED1LD0/LLN0.BR.brcbMeas01",
"rptId": "Meas",
"dataSet": "IED1LD0/LLN0.Measurements",
"reference": "IED1LD0/MMXU1.TotW",
"fc": "MX",
"reason": "dataChange",
"seqNum": "17",
"entryId": "0000000000000011",
"quality": "good",
"sourceTimestamp": "2026-11-20T10:14:03.24Z",
"serverTimestamp": "2026-11-20T10:14:03.31Z"
}
}
result Fields
| Field | Description |
|---|---|
reference, fc | The data set member: its reference (no FC) and functional constraint |
value | The member's value; for a data object, its main attribute (stVal, mag.f, ...) or the whole object |
valuePath, type, attributes | Where value sits in the member, its type, and the whole data object (null for an attribute) |
quality, flags | The IEC quality as a band and bit by bit; null when the member carries none |
reason | Why the IED included the member: dataChange, qualityChange, dataUpdate, integrity, generalInterrogation (several comma-separated); null when the RCB sends no reasons |
report | The report: rcb, rptId, dataSet, seqNum, entryId (buffered only), confRev, bufferOverflow, timestamp |
sourceTimestamp | The member's t (or its data object's t beside it in the same report), in UTC; null when there is none or the clock failed |
serverTimestamp | When MaestroHub received the report |
detail | Type-specific detail: timeQuality (the time quality bits of t) and, for a double point status, state (intermediate, off, on, bad) |
_metadata Fields
Every _metadata value is a string, including the numeric ones.
| Field | Description |
|---|---|
type | Always "iec61850_trigger". |
protocol | Always "iec61850". |
connectionId, functionId | The connection and the Receive Reports function. |
rcb, rptId, dataSet | The RCB, its report ID and data set. |
reference, fc | The member. |
reason | The reason for inclusion; absent when the RCB sends none. |
seqNum | The report's sequence number; absent when the RCB does not send it. |
entryId | The buffered report's entry ID (hex); absent for an unbuffered RCB. |
sourceTimestamp | Present only when the member carries a time whose clock has not failed. |
serverTimestamp | When MaestroHub received the report. |
quality | The member's band. Absent when it carries no quality. bad also on a failure event: once per outage, when the association is lost, the trigger fires with quality: "bad", quality_reason: "comm_error" and the cause under error; its result is the last member this trigger delivered, without sourceTimestamp. |
quality_reason, error | Only on a failure event. |
timestamp | When the trigger event was created, UTC. |
Referencing in Downstream Nodes
$trigger.result.value: the member's value$trigger.result.referenceand$trigger.result.fc: which member$trigger.result.quality:good,uncertainorbad$trigger.result.reason: why it was reported$trigger.result.sourceTimestamp: the device's timestamp, ornull$trigger._metadata.quality: the band, including the once-per-outagebadfailure event
Usage Examples
Measurements into the UNS
A Receive Reports function on the feeder's buffered RCB with dataChange, integrity, generalInterrogation, then a UNS Publish node under site/feeder7/{{$trigger.result.reference}}.
Breaker trips to the maintenance channel
A Receive Reports function on the status RCB, then a condition on $trigger.result.reference ending in .Op and $trigger.result.value true.
Best Practices
- Use a buffered RCB for data you store: it keeps reporting while the connection is down.
- Keep General Interrogation on, so every member's current value is known after each connect.
- Use one RCB instance per MaestroHub connection; other clients (a SCADA, a station gateway) use their own.