ABB Totalflow Nodes

Read the registers of ABB Totalflow flow computers and RTUs from a pipeline.

Operations
Read Register · Read Registers
Limits
One register a request; up to 100 in one node
Writes
None: reads only

Use ABB Totalflow devices in pipelines. Each function authored on an ABB Totalflow connection is available as a matching node in the Pipeline Designer: ABB Totalflow Read Register and ABB Totalflow Read Registers.

For connection setup (the station ID, the read security code and the waits), the register addresses and the data types, see the ABB Totalflow connection guide.

A Totalflow device does not send data on its own, so there is no trigger node: to poll one, drive the reads from a Schedule trigger.

Configuration Quick Reference​

FieldWhat you chooseDetails
ParametersConnection, Function, Function Parameters, Timeout OverrideSelect the ABB Totalflow connection, pick a function, bind parameters with expression support, and optionally override the timeout.
SettingsDescription, Timeout (seconds), Retry on Timeout, Retry on Fail, On ErrorNode description, maximum execution time, retry behaviour and error strategy. All execution settings default to pipeline-level values.

Every node shares the same Parameters: Connection (the ABB Totalflow connection profile), Function (a function of the node's type on that connection), Function Parameters (auto-populated from the function schema, with expression syntax {{ expression }} for dynamic values) and an optional Timeout Override in seconds. Each node receives the output of the previous node as input, which function parameter expressions can reference as $input.

The call's own facts ride along under _metadata next to the four every connected node carries. Every ABB Totalflow node delivers _metadata.method (the operation that ran, e.g. totalflow.read.register), _metadata.connectionId (the connection it ran over) and _metadata.protocol (totalflow).


ABB Totalflow Read Register nodeABB Totalflow Read Register node

Read Register node

ABB Totalflow Read Register Node​

Supported Function Types:

NodeFunctionPurposeCommon Use Cases
ABB Totalflow Read Register (connected.totalflow.read.register)totalflow.read.registerRead one register of a Totalflow device as a typed valueA meter run's flow rate on a schedule, a battery voltage, an alarm count

The node reads the register the function names, as its data type. See Read Register for the parameters and Registers and data types for the types.

Output Structure​

{
"result": {
"register": "11.7.0",
"dataType": "REAL",
"value": 1523.25,
"quality": "good"
}
}
KeyMeaning
result.registerThe register read, as Application.Array.Register: 011.07.0 comes back as 11.7.0
result.dataTypeThe type the value was decoded as, one of SINT, USINT, INT, WORD, DINT, DWORD, REAL, LINT, ULINT, LREAL
result.valueThe register's value, a number
result.qualitygood. A register the device refuses, or one of another width than the data type, fails the node instead of storing a value

Read a value with $node["Flow Rate"].result.value.


ABB Totalflow Read Registers nodeABB Totalflow Read Registers node

Read Registers node

ABB Totalflow Read Registers Node​

Supported Function Types:

NodeFunctionPurposeCommon Use Cases
ABB Totalflow Read Registers (connected.totalflow.read.registers)totalflow.read.registersRead many named registers of a Totalflow device in one nodeA meter run's flow rate, pressures and temperature together

The node reads every register of the function, one request each, and returns each value by its name. A register the device refuses is reported by name without failing the others; the read stops at the first register that finds the device out of reach (no connection, or no answer at all), keeps every value already read and reports the rest with that reason; the node fails as a whole only when nothing was read and the device answered nothing. See Read Registers for the parameters.

Output Structure​

When every register was read:

{
"result": {
"count": 2,
"values": { "FlowRate": 1523.25, "StaticPressure": 612.5 },
"quality": "good",
"totalRegisters": 2
}
}

When a register was not read, it is missing from values, its reason is in errors under its name, and quality is bad:

{
"result": {
"count": 2,
"values": { "FlowRate": 1523.25, "StaticPressure": 612.5 },
"errors": {
"Spare": "totalflow: register 11.7.9 is 2 bytes wide, a REAL is 4: read it as one of INT, WORD"
},
"quality": "bad",
"totalRegisters": 3
}
}
KeyMeaning
result.valuesEvery register that was read, by its name
result.errorsThe reason for each register that was not read, by its name. Present only when a register was not read
result.countHow many registers were read
result.totalRegistersHow many registers were requested
result.qualitygood when every register was read, bad when one was not

Read a register with $node["Meter Run 1"].result.values.FlowRate. Check $node["Meter Run 1"].result.errors before relying on every register being present.


Errors​

ErrorMeaningRetried by the node settings?
cannot open a connection to …The device cannot be reachedYes
the station at … did not answer … or … closed the connection …No whole reply: the device is slow or out of reach, or the station ID or security code is not the device'sYes
the device answered as station "X", not "Y" …Another device answers at this addressNo: the result is permanent
the station refused the read …The device did not carry out the read, usually a register it does not haveNo
register … is n bytes wide …The data type has another width than the registerNo
A refusal before anything is sent (a register that is no Application.Array.Register address, a missing data type)MaestroHub refused the request; nothing reached the deviceNo
not connected to the Totalflow deviceThe connection is downYes

The full list of messages, with what to change for each, is in the guide's Troubleshooting.


Settings Tab​

All ABB Totalflow node types share the same Settings tab:

SettingTypeDefaultDescription
DescriptionText-Optional description displayed on the node
Timeout (seconds)NumberPipeline defaultMaximum time the node may run before timing out
Retry on TimeoutTogglePipeline defaultAutomatically retry the node if it times out
Retry on FailTogglePipeline defaultAutomatically retry the node if it fails
On ErrorSelectionPipeline defaultError strategy: Pipeline Default (the pipeline's Error Handling setting), Stop Pipeline or Continue Execution

When left at their defaults, these settings inherit from the pipeline-level execution configuration. The retry settings do not retry a read the device refused for the read itself (see Errors).

Test before wiring

Use the Test button in the function form (on the connection page) to run every ABB Totalflow function against the live device before wiring it into a pipeline. It is the fastest way to catch a wrong station ID or security code, a register the device does not have, or the wrong data type.