Alstom Redundant Ethernet Nodes
Read and write Alstom controllers over up to four redundant Ethernet paths, from a pipeline.
- Operations
- Read Coils · Read Discrete Inputs · Read Holding Registers · Read Input Registers · Write Coils · Write Holding Registers
- Limits
- 800 bits or 62 registers a request; last address 9999
- Writes
- Never re-sent, never buffered
Use Alstom controllers on redundant Ethernet in pipelines. Each function authored on an Alstom Redundant Ethernet connection is available as a matching node in the Pipeline Designer.
For connection setup (the paths, the station ID, the local interfaces), the addresses and the limits of one request, see the Alstom Redundant Ethernet connection guide.
The controller does not send data on its own, so there is no trigger node: to poll it, drive the reads from a Schedule trigger.
Configuration Quick Reference
| Field | What you choose | Details |
|---|---|---|
| Parameters | Connection, Function, Function Parameters, Timeout Override | Select the Alstom Redundant Ethernet connection, pick a function, bind parameters with expression support, and optionally override the timeout. |
| Settings | Description, Timeout (seconds), Retry on Timeout, Retry on Fail, On Error | Node description, maximum execution time, retry behaviour and error strategy. All execution settings default to pipeline-level values. A write node is never re-sent, whatever these settings say. |
Every node shares the same Parameters: Connection (the Alstom Redundant Ethernet connection profile), Function (a function of the node's type on that connection), Function Parameters (auto-populated from the function schema, with expression syntax {{ expression }} for dynamic values) and an optional Timeout Override in seconds. Each node receives the output of the previous node as input, which function parameter expressions can reference as $input.
The call's own facts ride along under _metadata next to the four every connected node carries. Every Alstom Redundant Ethernet node delivers _metadata.method (the operation that ran, e.g. alstomredundant.read.holdingRegisters) and _metadata.paths (how many paths took the request: fewer than configured means a path is down). A read also delivers _metadata.bytesRead (the data bytes of the reply), a write _metadata.bytesWritten (the data bytes sent).


Read Coils node
Alstom Redundant Ethernet Read Coils and Read Discrete Inputs Nodes
Supported Function Types:
| Node | Function | Purpose | Common Use Cases |
|---|---|---|---|
Alstom Redundant Ethernet Read Coils (connected.alstomredundant.read.coils) | alstomredundant.read.coils | Read the ON/OFF state of coils (FC 01) | Relay and command states |
Alstom Redundant Ethernet Read Discrete Inputs (connected.alstomredundant.read.discreteInputs) | alstomredundant.read.discreteInputs | Read the ON/OFF state of discrete inputs (FC 02) | Breaker positions, limit switches, alarm bits |
The node reads up to 800 contiguous bits over every open path and returns the first valid reply.
Output Structure
{
"result": {
"address": 10,
"quantity": 3,
"coils": [true, false, true],
"value": [true, false, true],
"raw": "BQ=="
}
}
A discrete input read carries inputs instead of coils.
| Key | Meaning |
|---|---|
result.address | The start address that was read |
result.quantity | How many bits were read |
result.coils | One boolean per coil, in address order (Read Coils) |
result.inputs | One boolean per discrete input, in address order (Read Discrete Inputs) |
result.value | The reading: the same list of booleans |
result.raw | The raw data bytes of the reply, base64-encoded |


Read Holding Registers node
Alstom Redundant Ethernet Read Holding Registers and Read Input Registers Nodes
Supported Function Types:
| Node | Function | Purpose | Common Use Cases |
|---|---|---|---|
Alstom Redundant Ethernet Read Holding Registers (connected.alstomredundant.read.holdingRegisters) | alstomredundant.read.holdingRegisters | Read holding registers (FC 03) | Setpoints, configuration values, computed measurements |
Alstom Redundant Ethernet Read Input Registers (connected.alstomredundant.read.inputRegisters) | alstomredundant.read.inputRegisters | Read input registers (FC 04) | Live measurements, counters |
The node reads up to 62 contiguous registers over every open path and decodes them as the function's data type and byte order. See Addresses and the limits of one request.
Output Structure
{
"result": {
"address": 100,
"quantity": 2,
"registers": [16712, 0],
"value": 12.5,
"dataType": "float32",
"byteOrder": "ABCD",
"raw": "QUgAAA=="
}
}
| Key | Meaning |
|---|---|
result.address | The start address that was read |
result.quantity | How many registers were read |
result.registers | The raw 16-bit register values, in address order |
result.value | The reading: the registers decoded as dataType (the registers themselves for raw) |
result.dataType | The data type the registers were decoded as |
result.byteOrder | The byte order applied before decoding: ABCD, CDAB, BADC or DCBA |
result.raw | The raw data bytes of the reply, base64-encoded |
Read a value with $node["Feeder Current"].result.value.


Write Holding Registers node
Alstom Redundant Ethernet Write Coils and Write Holding Registers Nodes
Supported Function Types:
| Node | Function | Purpose | Common Use Cases |
|---|---|---|---|
Alstom Redundant Ethernet Write Coils (connected.alstomredundant.write.multipleCoils) | alstomredundant.write.multipleCoils | Write ON/OFF values to contiguous coils (FC 15) | Command outputs |
Alstom Redundant Ethernet Write Holding Registers (connected.alstomredundant.write.multipleRegisters) | alstomredundant.write.multipleRegisters | Write values to contiguous holding registers (FC 16) | Setpoints, operating modes |
The node writes the function's list of values (up to 800 coils or 62 registers) on every open path. Each write goes out on every open path, so each board receives it once per network; the board is expected to drop the second copy by its sequence number, including in the rounds right after a connect or a sequence reset, when the request carries sequence 0. That is the vendor driver's design, not yet confirmed on a real controller (#8737).
When no valid reply comes, a board may still have carried the write out on a redundant path. The node then fails with Alstom write failed; delivery may have occurred on a redundant path and is not replayed, and nothing sends it again: not Retry on Fail, not a ForEach retry. A write is never buffered for later delivery, and it is refused in a run started by a late (replayed) input unless the node allows late input.
Output Structure
{
"result": {
"address": 40,
"quantity": 2,
"values": [11, 22],
"raw": "ACgAAg=="
}
}
| Key | Meaning |
|---|---|
result.address | The address that was written |
result.quantity | How many coils or registers were written |
result.values | The values that were written, as sent |
result.raw | The raw data bytes of the reply (the echoed address and quantity), base64-encoded |
Always validate values in a Condition node before writing to a controller. A setpoint or a command can move equipment immediately.
Errors
| Error | Meaning | Retried by the node settings? |
|---|---|---|
Alstom response timeout: no valid Alstom response | No valid reply on any path in time | Reads: yes. Writes: never |
Alstom write failed; delivery may have occurred on a redundant path and is not replayed | A write's outcome is unknown | Never |
modbus: exception '2' (illegal data address) | The controller refused the request | No |
… the Alstom core block limit is 62 registers / 800 bits | The request is too long. Nothing was sent | No |
… Alstom addresses end at 9999 | The request goes past address 9999. Nothing was sent | No |
not connected to the Alstom controller | Every path is closed | Yes, after reconnect |
See the connection guide's error reference for every message.