Alstom Redundant Ethernet Nodes

Read and write Alstom controllers over up to four redundant Ethernet paths, from a pipeline.

Operations
Read Coils · Read Discrete Inputs · Read Holding Registers · Read Input Registers · Write Coils · Write Holding Registers
Limits
800 bits or 62 registers a request; last address 9999
Writes
Never re-sent, never buffered

Use Alstom controllers on redundant Ethernet in pipelines. Each function authored on an Alstom Redundant Ethernet connection is available as a matching node in the Pipeline Designer.

For connection setup (the paths, the station ID, the local interfaces), the addresses and the limits of one request, see the Alstom Redundant Ethernet connection guide.

The controller does not send data on its own, so there is no trigger node: to poll it, drive the reads from a Schedule trigger.

Configuration Quick Reference​

FieldWhat you chooseDetails
ParametersConnection, Function, Function Parameters, Timeout OverrideSelect the Alstom Redundant Ethernet connection, pick a function, bind parameters with expression support, and optionally override the timeout.
SettingsDescription, Timeout (seconds), Retry on Timeout, Retry on Fail, On ErrorNode description, maximum execution time, retry behaviour and error strategy. All execution settings default to pipeline-level values. A write node is never re-sent, whatever these settings say.

Every node shares the same Parameters: Connection (the Alstom Redundant Ethernet connection profile), Function (a function of the node's type on that connection), Function Parameters (auto-populated from the function schema, with expression syntax {{ expression }} for dynamic values) and an optional Timeout Override in seconds. Each node receives the output of the previous node as input, which function parameter expressions can reference as $input.

The call's own facts ride along under _metadata next to the four every connected node carries. Every Alstom Redundant Ethernet node delivers _metadata.method (the operation that ran, e.g. alstomredundant.read.holdingRegisters) and _metadata.paths (how many paths took the request: fewer than configured means a path is down). A read also delivers _metadata.bytesRead (the data bytes of the reply), a write _metadata.bytesWritten (the data bytes sent).


Alstom Redundant Ethernet Read Coils nodeAlstom Redundant Ethernet Read Coils node

Read Coils node

Alstom Redundant Ethernet Read Coils and Read Discrete Inputs Nodes​

Supported Function Types:

NodeFunctionPurposeCommon Use Cases
Alstom Redundant Ethernet Read Coils (connected.alstomredundant.read.coils)alstomredundant.read.coilsRead the ON/OFF state of coils (FC 01)Relay and command states
Alstom Redundant Ethernet Read Discrete Inputs (connected.alstomredundant.read.discreteInputs)alstomredundant.read.discreteInputsRead the ON/OFF state of discrete inputs (FC 02)Breaker positions, limit switches, alarm bits

The node reads up to 800 contiguous bits over every open path and returns the first valid reply.

Output Structure​

{
"result": {
"address": 10,
"quantity": 3,
"coils": [true, false, true],
"value": [true, false, true],
"raw": "BQ=="
}
}

A discrete input read carries inputs instead of coils.

KeyMeaning
result.addressThe start address that was read
result.quantityHow many bits were read
result.coilsOne boolean per coil, in address order (Read Coils)
result.inputsOne boolean per discrete input, in address order (Read Discrete Inputs)
result.valueThe reading: the same list of booleans
result.rawThe raw data bytes of the reply, base64-encoded

Alstom Redundant Ethernet Read Holding Registers nodeAlstom Redundant Ethernet Read Holding Registers node

Read Holding Registers node

Alstom Redundant Ethernet Read Holding Registers and Read Input Registers Nodes​

Supported Function Types:

NodeFunctionPurposeCommon Use Cases
Alstom Redundant Ethernet Read Holding Registers (connected.alstomredundant.read.holdingRegisters)alstomredundant.read.holdingRegistersRead holding registers (FC 03)Setpoints, configuration values, computed measurements
Alstom Redundant Ethernet Read Input Registers (connected.alstomredundant.read.inputRegisters)alstomredundant.read.inputRegistersRead input registers (FC 04)Live measurements, counters

The node reads up to 62 contiguous registers over every open path and decodes them as the function's data type and byte order. See Addresses and the limits of one request.

Output Structure​

{
"result": {
"address": 100,
"quantity": 2,
"registers": [16712, 0],
"value": 12.5,
"dataType": "float32",
"byteOrder": "ABCD",
"raw": "QUgAAA=="
}
}
KeyMeaning
result.addressThe start address that was read
result.quantityHow many registers were read
result.registersThe raw 16-bit register values, in address order
result.valueThe reading: the registers decoded as dataType (the registers themselves for raw)
result.dataTypeThe data type the registers were decoded as
result.byteOrderThe byte order applied before decoding: ABCD, CDAB, BADC or DCBA
result.rawThe raw data bytes of the reply, base64-encoded

Read a value with $node["Feeder Current"].result.value.


Alstom Redundant Ethernet Write Holding Registers nodeAlstom Redundant Ethernet Write Holding Registers node

Write Holding Registers node

Alstom Redundant Ethernet Write Coils and Write Holding Registers Nodes​

Supported Function Types:

NodeFunctionPurposeCommon Use Cases
Alstom Redundant Ethernet Write Coils (connected.alstomredundant.write.multipleCoils)alstomredundant.write.multipleCoilsWrite ON/OFF values to contiguous coils (FC 15)Command outputs
Alstom Redundant Ethernet Write Holding Registers (connected.alstomredundant.write.multipleRegisters)alstomredundant.write.multipleRegistersWrite values to contiguous holding registers (FC 16)Setpoints, operating modes

The node writes the function's list of values (up to 800 coils or 62 registers) on every open path. Each write goes out on every open path, so each board receives it once per network; the board is expected to drop the second copy by its sequence number, including in the rounds right after a connect or a sequence reset, when the request carries sequence 0. That is the vendor driver's design, not yet confirmed on a real controller (#8737).

A write is never re-sent

When no valid reply comes, a board may still have carried the write out on a redundant path. The node then fails with Alstom write failed; delivery may have occurred on a redundant path and is not replayed, and nothing sends it again: not Retry on Fail, not a ForEach retry. A write is never buffered for later delivery, and it is refused in a run started by a late (replayed) input unless the node allows late input.

Output Structure​

{
"result": {
"address": 40,
"quantity": 2,
"values": [11, 22],
"raw": "ACgAAg=="
}
}
KeyMeaning
result.addressThe address that was written
result.quantityHow many coils or registers were written
result.valuesThe values that were written, as sent
result.rawThe raw data bytes of the reply (the echoed address and quantity), base64-encoded
Safety First

Always validate values in a Condition node before writing to a controller. A setpoint or a command can move equipment immediately.


Errors​

ErrorMeaningRetried by the node settings?
Alstom response timeout: no valid Alstom responseNo valid reply on any path in timeReads: yes. Writes: never
Alstom write failed; delivery may have occurred on a redundant path and is not replayedA write's outcome is unknownNever
modbus: exception '2' (illegal data address)The controller refused the requestNo
… the Alstom core block limit is 62 registers / 800 bitsThe request is too long. Nothing was sentNo
… Alstom addresses end at 9999The request goes past address 9999. Nothing was sentNo
not connected to the Alstom controllerEvery path is closedYes, after reconnect

See the connection guide's error reference for every message.