AutomationDirect ECOM Nodes
Read and write V memory, inputs, outputs and relays of DirectLOGIC PLCs from a pipeline, through their ECOM Ethernet module.
- Operations
- Read Device · Read Block · Write Device
- Limits
- 63 words a request; one bit per bit write
- Writes
- Sent once, whole or not at all; never buffered
Use DirectLOGIC PLCs in pipelines. Each function authored on an AutomationDirect ECOM connection is available as a matching node in the Pipeline Designer: AutomationDirect ECOM Read Device, AutomationDirect ECOM Read Block and AutomationDirect ECOM Write Device.
For connection setup (the module's address, the PLC model and the waits), the octal addresses and the data types, see the AutomationDirect ECOM connection guide.
A PLC does not send data on its own, so there is no trigger node: to poll one, drive the reads from a Schedule trigger.
Configuration Quick Reference
| Field | What you choose | Details |
|---|---|---|
| Parameters | Connection, Function, Function Parameters, Timeout Override | Select the AutomationDirect ECOM connection, pick a function, bind parameters with expression support, and optionally override the timeout. |
| Settings | Description, Timeout (seconds), Retry on Timeout, Retry on Fail, On Error | Node description, maximum execution time, retry behaviour and error strategy. All execution settings default to pipeline-level values. |
Every node shares the same Parameters: Connection (the AutomationDirect ECOM connection profile), Function (a function of the node's type on that connection), Function Parameters (auto-populated from the function schema, with expression syntax {{ expression }} for dynamic values) and an optional Timeout Override in seconds. Each node receives the output of the previous node as input, which function parameter expressions can reference as $input.
The call's own facts ride along under _metadata next to the four every connected node carries. Every AutomationDirect ECOM node delivers _metadata.method (the operation that ran, e.g. adecom.read.device), _metadata.connectionId (the connection it ran over) and _metadata.protocol (adecom).


Read Device node
AutomationDirect ECOM Read Device Node
Supported Function Types:
| Node | Function | Purpose | Common Use Cases |
|---|---|---|---|
AutomationDirect ECOM Read Device (connected.adecom.read.device) | adecom.read.device | Read one typed value, or a run of consecutive values, from an address | A part counter on a schedule, a timer's current value, a motor output |
The node reads the address the function names, as its data type, or Count consecutive values. See Read Device for the parameters and Addresses for the data types.
Output Structure
{
"result": {
"device": "V2000",
"dataType": "WORD",
"value": 1234,
"quality": "good"
}
}
With Count more than 1, value is a list.
| Key | Meaning |
|---|---|
result.device | The address read, in one standard octal form: v2000 comes back as V2000 |
result.dataType | The type the value was decoded as. An empty data type comes back as the address's own |
result.value | The value: a number, text for a STRING, or true/false for a bit. A list of values when Count is more than 1 |
result.quality | good. A refusal or a lost answer fails the node instead of storing a value, so a value that reached the result is the PLC's own reading |
Read a value with $node["Part Count"].result.value.


Read Block node
AutomationDirect ECOM Read Block Node
Supported Function Types:
| Node | Function | Purpose | Common Use Cases |
|---|---|---|---|
AutomationDirect ECOM Read Block (connected.adecom.read.block) | adecom.read.block | Read many typed datapoints in the fewest requests | A line's counters, setpoints and motor outputs in one node |
The node reads every point of the function and returns each value by its name. Points whose words lie close together are read in one request, with what lies between them, when it fits. A point that is refused, or outside the PLC model's memory, is reported by name without failing the others; the node fails only when the module does not answer at all. See Read Block for the parameters.
Output Structure
When every point was read:
{
"result": {
"count": 3,
"values": { "PartCount": 1234, "Rate": 21.5, "MotorOn": true },
"quality": "good",
"totalDataPoints": 3,
"totalReads": 2
}
}
Here PartCount (V2000) and Rate (V2002) share one request and MotorOn (Y0) takes a second.
When a point was not read, it is missing from values, its reason is in errors under its name, and quality is bad:
{
"result": {
"count": 2,
"values": { "PartCount": 1234, "MotorOn": true },
"errors": {
"Spare": "adecom: V50000 to V50000 is not inside one of the DL-260's V memory ranges (...)"
},
"quality": "bad",
"totalDataPoints": 3,
"totalReads": 2
}
}
| Key | Meaning |
|---|---|
result.values | Every point that was read, by its name |
result.errors | The reason for each point that was not read, by its name. Present only when a point was not read |
result.count | How many points were read |
result.totalDataPoints | How many points were requested |
result.totalReads | How many requests the points were merged into, including the requests that asked again point by point after a refusal |
result.quality | good when every point was read, bad when one was not |
Read a point with $node["Line 2"].result.values.PartCount. Check $node["Line 2"].result.errors before relying on every point being present.


Write Device node
AutomationDirect ECOM Write Device Node
Supported Function Types:
| Node | Function | Purpose | Common Use Cases |
|---|---|---|---|
AutomationDirect ECOM Write Device (connected.adecom.write.device) | adecom.write.device | Write one typed value, or a run of consecutive values, to an address | Setpoints, recipes, a control relay the PLC program watches |
The node writes the function's value, or a list of values to consecutive V words, in one request of at most 63 words; or sets or resets one bit with the PLC's own bit command. A bit inside a V word cannot be written alone. The write is sent once. See Write Device for the parameters and the write rules.
A write is never buffered for later delivery, and it is refused in a run started by a late (replayed) input unless the node allows late input. A value that does not fit its type fails the node before anything is sent to the PLC.
Output Structure
{
"result": {
"device": "V2100",
"dataType": "REAL",
"value": "21.5"
}
}
| Key | Meaning |
|---|---|
result.device | The address written, in one standard octal form: v2100 comes back as V2100 |
result.dataType | The type the value was encoded as |
result.value | The value as given, after parameter substitution: "21.5", or the list "[120, 45, 3]" |
Always validate values in a Condition node before writing to a PLC. A setpoint or an output can move a machine immediately.
Errors
| Error | Meaning | Retried by the node settings? |
|---|---|---|
no answer from the ECOM module … | No answer to any attempt: the module is off or out of reach | Yes. A write sent again leaves the PLC as one write of the same value does |
… acknowledged the request but the PLC's answer did not come … | The module took the request; the PLC's completion did not arrive. A write may have been carried out | Yes |
the ECOM module refused the request … / the PLC did not complete the request … | A refusal, with its status code. AutomationDirect does not publish what the codes mean | Yes |
| A refusal before anything is sent (an address that is no address, outside the PLC model's memory, a data type the address does not hold, a bit inside a V word, a value its type cannot hold, a list too long for one request) | MaestroHub refused the request; nothing reached the PLC | No |
not connected to the ECOM module | The connection is down | Yes |
The full list of messages, with what to change for each, is in the guide's Troubleshooting.
Settings Tab
All AutomationDirect ECOM node types share the same Settings tab:
| Setting | Type | Default | Description |
|---|---|---|---|
| Description | Text | - | Optional description displayed on the node |
| Timeout (seconds) | Number | Pipeline default | Maximum time the node may run before timing out |
| Retry on Timeout | Toggle | Pipeline default | Automatically retry the node if it times out |
| Retry on Fail | Toggle | Pipeline default | Automatically retry the node if it fails |
| On Error | Selection | Pipeline default | Error strategy: Pipeline Default (the pipeline's Error Handling setting), Stop Pipeline or Continue Execution |
When left at their defaults, these settings inherit from the pipeline-level execution configuration. The retry settings do not retry a request MaestroHub refused before sending (see Errors).
Use the Test button in the function form (on the connection page) to run every AutomationDirect ECOM function against the live PLC before wiring it into a pipeline. It is the fastest way to catch a wrong PLC model, an address the PLC does not have, or a BCD value read as WORD.