Skip to main content
Version: 3.2

Siemens SINUMERIK 808DSINUMERIK808DSIEMENS Siemens SINUMERIK 808D Integration Guide

Read the PLC memory of SINUMERIK 808D machine tools, write setpoints to it, and send commands the PLC program acts on.

Status
Beta
Protocol
S7 (ISO-on-TCP), port 102
Operations
Read Points · Write Point · Send Command
Triggers
None: poll with a Schedule trigger

A SINUMERIK 808D CNC has an integrated PLC built on the S7-200. On its Ethernet port, that PLC accepts S7 clients by a TSAP pair. MaestroHub reads and writes the PLC memory by address. This covers the data blocks that hold the NC/PLC interface signals and user data, the flags (M), inputs (I), outputs (Q), system flags (SM), and the IEC counters (C) and timers (T). This guide covers the connection, the addresses, the three function types and their pipeline nodes.

The NC itself (axis positions, NC variables, alarms of the NCK) is not reached this way. MaestroHub sees what the PLC program sees.

Beta

What stands behind the connector today:

  • The connect sequence, the address grammar, the area bounds and the value encodings follow a reference driver for the 808D, read byte by byte.
  • The area codes of the S7-200 family (system flags 0x05, IEC counters 0x1E, IEC timers 0x1F) and the way a counter or timer is addressed agree with two public sources: Wireshark's S7comm dissector and libnodave.
  • MaestroHub's S7 stack is the one its Siemens S7 and LOGO! connectors use. Its tests run in three places: against an in-process test PLC that checks every request byte by byte; against an independent S7 server (snap7) for data blocks, flags, inputs and outputs; and against Wireshark's own reading of the requests.

What is not proven yet:

  • It has not been run against a real 808D. The checks still owed are listed in issue #8824.
  • The meaning of an IEC timer's value and of the status byte of a counter or timer beyond "set or not". MaestroHub reports both as the PLC sends them.
  • Counters and timers are read, not written: how the 808D takes a written counter or timer is not confirmed.

Overview​

The SINUMERIK 808D connector provides:

  • Addresses as the PLC uses them: DB3800/2.1, M10.0, I0.3, Q1, SM0.5, C5, T12/STATUS
  • Typed values: BIT, SINT, BYTE, INT, WORD, DINT, DWORD and REAL, big-endian as S7 sends them
  • Many points in the fewest requests: neighbouring points of one area share a request
  • Setpoint writes, and commands that are sent at most once
  • Bits written as bits: the other bits of the byte, which the PLC program may be changing, are never rewritten

Connection Configuration​

Creating a SINUMERIK 808D Connection​

Navigate to Connections → New Connection → Siemens SINUMERIK 808D.

SINUMERIK 808D connection creation formSINUMERIK 808D connection creation form

The SINUMERIK 808D connection form

FieldDefaultDescription
Address-The 808D's IP address or host name (required)
Port102S7 (ISO-on-TCP) port. The 808D serves 102.
Local TSAP02.00MaestroHub's TSAP, two hex bytes
Remote TSAP01.02The 808D's TSAP, two hex bytes
Timeout5sMaximum time to connect, and to wait for each answer

The TSAP defaults are the ones the reference 808D driver uses. A TSAP is two hex bytes separated by a dot.

Testing the Connection​

Test Connection opens the S7 connection with the TSAPs, negotiates the PDU and reads the system flag byte SMB0. A refused read still counts as an answer, because it proves an S7 PLC replied.

Addresses​

An address is at most 48 characters, without spaces; letters may be lower case. A bit is byte.bit. A byte address needs a data type, and the value must end inside its area.

AddressWhat it isRangeTypesWritten
DB<n>/<byte>[.<bit>]Data blockDB1-65535, bytes 0-10239BIT, or any typeYes
M<byte>[.<bit>]Flagsbytes 0-255BIT, or any typeYes
I<byte>[.<bit>]Inputsbytes 0-15BIT, or any typeNo
Q<byte>[.<bit>]Outputsbytes 0-15BIT, or any typeYes
SM<byte>[.<bit>]System flagsbytes 0-549BIT, or any typeBytes and words from SMB30 (SMB0-SMB29 and the bits are the CPU's status)
C<n> / C<n>/STATUSIEC counterC0-255WORD / BITNo
T<n> / T<n>/STATUSIEC timerT0-255DWORD / BITNo

The types: SINT (−128-127), BYTE (0-255), INT (−32768-32767), WORD (0-65535), DINT and DWORD (32-bit signed and unsigned), REAL (32-bit floating point; a NaN or infinity is refused, both read and written).

The NC/PLC interface signals

The PLC Programming Tool writes a data block address as one V number. In V38000002.1, the first four digits are the data block, the next four the byte, and .1 the bit: DB3800/2.1 here.

Function Builder​

SINUMERIK 808D function type pickerSINUMERIK 808D function type picker

The three function types

Read Points (sinumerik808d.read)​

Read a set of named points, each by its 808D address, in the fewest requests.

FieldRequiredDescription
PointsYesOne to 100 {name, address, dataType}. The name is the key in the result. A bit, a counter, a timer and a /STATUS need no data type. More points go in several functions.

Example: spindleRunning = DB3800/2.1, partCount = DB1000/20 as DINT returns { "spindleRunning": true, "partCount": 1520 } under values.

A point name may not repeat, and an address the 808D does not have (such as M256, or DB1/10239 as INT) is refused when the function is saved.

Write Point (sinumerik808d.write)​

Write one setpoint: a value the PLC program reads as a setting.

FieldRequiredDescription
AddressYesA data block, flag or output address, or a system flag byte or word from SMB30: DB1000/40, M12.3, Q1, SM34. Supports ((paramName)).
Data TypeFor a byte addressThe type the address holds, in upper case (INT, not int) when the function is created through the API. With a ((paramName)) address, choose the type it will hold, or Set by the address for a bit bound at run time; a byte address bound without a type is refused when the function runs.
ValueYestrue/false (also on/off, 1/0) for a bit; a number the type holds otherwise. It is checked against the data type when the function is saved; with a ((paramName)) address and no data type (Set by the address), when the function runs. Supports ((paramName)), checked when the function runs.
A Write Point value taken from a parameterA Write Point value taken from a parameter

A value written from a ((parameter))

Writing the same value again leaves the address as it was. So a write whose answer was lost may be sent again, under Retry on Fail.

Send Command (sinumerik808d.command)​

Send one value the PLC program acts on and then clears, such as a request bit (M20.0 set to true) or a job number. Its fields are those of Write Point.

A command is sent at most once

If the 808D does not answer a command in time, MaestroHub never sends it again on its own: the program may already have acted on it. The node fails with the outcome unknown, so a person or the pipeline can check the machine and decide. Use Write Point for setpoints, which are safe to repeat.

Testing Functions​

Test Function on the function form runs the read, write or command against the live 808D. A test of a write or a command changes the machine's PLC memory, and the dialog says so.

Pipeline Integration​

Each operation has its own node: Siemens SINUMERIK 808D Read Points, Write Point and Send Command. See Siemens SINUMERIK 808D Nodes for their parameters and results. To poll the 808D, start the pipeline with a Schedule trigger.

SINUMERIK 808D node in the pipeline designerSINUMERIK 808D node in the pipeline designer

The Read Points node with its connection and function

Common Use Cases​

  • Machine state to the UNS: read the interface signals of the mode group and channel every few seconds, and publish them to the machine's UNS topic.
  • Part counting: read a part counter the PLC program keeps in a data block, or an IEC counter, and write the count to the historian.
  • Order hand-over: write a job number with Send Command and let the PLC program pick it up.

Troubleshooting​

SymptomPossible causeSolution
Test Connection fails at onceAnother TSAP pair, port or addressCheck the address and the TSAPs the 808D accepts
the object does not exist (return code 0x0A)The data block does not exist in this PLC programCheck the DB number in the PLC Programming Tool
the address is out of range (return code 0x05)The address lies past the end of what the PLC hasCheck the byte and the data type's width
access to the object is not allowed (return code 0x03)The PLC protects this memoryWrite an address the PLC program reads as a setting
address "…" is a byte address: give its dataType (SINT, BYTE, INT, WORD, DINT, DWORD or REAL), or address a bit as byte.bitA byte address without a data type (the form says … is a byte address: choose its data type)Choose the type, or address a bit as byte.bit
inputs are read-only (or read-only for SM)A write to I, an SM bit or SMB0-SMB29, a counter or a timerWrite a flag, output or data block address the program reads