LS Electric XGTXGT LS Electric XGT Integration Guide

Read and write the memory of LS Electric XGK, XGB, XGI, XGR and XEC PLCs by the addresses XG5000 shows, over FEnet or Cnet.

Status
Beta
PLC families
XGK · XGB · XGI · XGR · XEC
Transports
FEnet (TCP 2004) · Cnet on a serial line · Cnet over TCP
Operations
Read Device · Read Block · Write Device
Triggers
None: poll with a Schedule trigger

LS Electric PLCs (formerly LSIS, and before that LG) answer the XGT dedicated protocol, which LS publishes in two forms: FEnet, a binary form on TCP port 2004 of a FEnet module or a CPU's built-in Ethernet port, and Cnet, the same commands as text on a serial channel. MaestroHub reads and writes the PLC's devices by the addresses XG5000 shows: D00100 and M0172C on an XGK or XGB, %MW100 and %IX0.0.3 on an XGI, XGR or XEC. This guide covers the connection, the two transports and how to set up the PLC for each, the device addresses, the three function types, and the matching pipeline nodes.

Beta

What stands behind the connector today:

  • It follows LS's own manuals: the XGT FEnet I/F manual (V3.62), the XGB FEnet I/F manual (V2.1) and the XGB Cnet I/F manual (V2.4).
  • Its requests were answered correctly by two PLC simulators that other people wrote from the same manuals: VagabondK.Protocols' FEnet and Cnet simulators, over TCP and over a serial line, with and without the Cnet checksum, and testbench-plc-sim's FEnet and Cnet. HslCommunication's FEnet server answered a smoke test. Three independent clients (VagabondK's, HslCommunication's and Devinno's) read and wrote the test PLC that MaestroHub's own tests use.

What is not proven yet:

  • It has not been run against a real LS PLC of any family, nor over a real serial cable. The serial line was tested through a pseudo-terminal.
  • How a bit of an XGK or XGB word device is named. LS's FEnet manuals and its XGB Cnet manual give two different forms, and only a real PLC can say which one each model takes. See Bit names on the wire.
  • The layout of a STRING. LS's manuals give none for these commands. MaestroHub reads and writes a STRING as the device's bytes in memory order, the first character in the low byte of the first word, filled with zero bytes after the text. It has not been checked against a string a PLC program wrote.
  • The FEnet status request, which every FEnet connection starts with, is proven against LS's manual and MaestroHub's own test PLC only: no simulator answers it.
  • A dotted address on Cnet (%IX0.0.3, U01.02): LS's Cnet manual lists these devices in that form but leaves the dot out of the characters a name may have. A real XEC will settle it.

Overview​

The LS Electric XGT connector provides:

  • Five PLC families: XGK and XGB with letter devices, XGI, XGR and XEC with IEC addresses
  • Every PLC data type: BIT, WORD, INT, DWORD, DINT, REAL, LREAL and STRING
  • Safe bit writes: a bit is written as a bit, never by reading its word and writing it back
  • Block reads: many named devices in one node, sixteen devices of one size to a request
  • Three transports: FEnet on TCP, Cnet on a serial line of the MaestroHub host, and Cnet over TCP through a serial gateway
  • Cnet with its checksum by default, or without
  • System flags protected: F and N are refused for writing before anything is sent

Terms used in this guide​

TermMeaning
XGT dedicated protocolLS's published protocol for reading and writing a PLC's devices. It has two forms, FEnet and Cnet, with the same commands.
FEnetThe binary form, on TCP port 2004 of a FEnet module (XGL-EFMT and its kin on XGK, XGI and XGR; XBL-EMTA on XGB) or of a CPU's built-in Ethernet port.
CnetThe text form, on an RS-232C or RS-485 channel: a built-in Cnet channel of an XGB CPU, or a Cnet I/F module. Up to 32 PLCs share one RS-485 line, each with its own station number.
XGT serverThe operating mode a Cnet channel must be set to in XG5000 so that it answers these commands.
Loader portThe CPU's engineering port that XG5000 uses. Its protocol is not published, and MaestroHub does not use it.
DeviceA memory area of the PLC and an address in it: D00100 is data register 100, M0172C is bit C of auxiliary relay word 172, %MW100 is IEC memory word 100.

Supported PLCs​

PLC FamilyPLCsAddresses
XGKXGK CPUsLetter devices as XG5000 shows them: D00100, M0172C, T0005, U01.02
XGBXGB CPUs with letter devices (XBM, XBC)Letter devices, as on the XGK
XGIXGI CPUsIEC addresses: %MW100, %MD50, %MX2764, %IX0.0.3
XGRXGR redundant CPUsIEC addresses, as on the XGI
XECXGB CPUs with IEC addresses (XEC)IEC addresses, as on the XGI

The older Master-K and GLOFA-GM lines are not supported.

FEnet or Cnet?​

FEnetCnet on a serial lineCnet over TCP
ReachesA FEnet module, or a CPU's built-in Ethernet portA Cnet channel wired to a serial port of the MaestroHub hostA Cnet channel behind a serial-to-Ethernet gateway, or a FEnet module in XGT server mode
PortTCP 2004The host's serial deviceThe gateway's TCP port
IntegrityTCP, and a checksum of each headerA checksum of each frame, on by defaultA checksum of each frame, on by default
Data in one request1400 bytes (500 on an XGB or XEC)60 words read, 58 or 59 written60 words read, 58 or 59 written
PLC setupNone beyond the module's IP addressThe channel set to XGT server, its speed, parity and station numberAs for the serial line, on the channel behind the gateway

Choose FEnet whenever the PLC is on Ethernet: it carries more data per request and needs no channel setting. Choose Cnet for a PLC that has only serial channels, or one already wired to an RS-485 line.

Not supported​

WhatWhy
The loader portNot published by LS, and no software but XG5000 speaks it. Every PLC that has one also has Cnet or FEnet. See Moving off the loader port.
FEnet over UDP (port 2005)Not in this version.
The ZR deviceNo LS manual gives its name on the wire. On an XGB, R is the same memory.
A bit of D, R, Z or N on its own (D00100.3)LS gives these devices byte and word access only. Read the word as WORD and take the bit from the value.
The S deviceNo LS table of the XGK or XGB lists it for these commands.
Writing F (system flags) or NLS lists them for reading and monitoring only. A write is refused before anything is sent.
Tag names (symbolic variables)The protocol takes device addresses only. Take the address of a variable from XG5000.
A triggerThese PLCs do not send data on their own. Poll them with a Schedule trigger.

What happens on connect​

For FEnet, MaestroHub opens the TCP connection and sends the FEnet status request, which every FEnet module answers with the PLC's type and operating mode. For Cnet, it opens the serial port or the TCP connection and reads the first word of the system flags (%FW0). Any answer counts, also a refusal: it proves that an XGT server is listening. An open TCP port or serial port alone proves nothing, because a serial port opens whether or not anything is wired to it.

The connection sends one request at a time. A FEnet reply must carry the request's invoke number and command; a Cnet reply must carry the request's station number and command. Anything else closes the connection, which is then opened again. Use one MaestroHub connection per PLC on FEnet, and one per serial line on Cnet.

Connection Configuration​

Creating an LS Electric XGT Connection​

Navigate to Connections → New Connection → LS Electric XGT and fill in the form. It has four tabs: Connection, Functions, Scaling and Health. The Functions, Scaling and Health tabs unlock after the connection is saved.

1. Profile Information​

FieldDefaultDescription
Profile Name-A descriptive name for this connection profile (required). Must be unique across all connections.
Description-Optional description for this connection
Labels-Key-value pairs to categorize and organize the connection

Example Labels

  • line: press-3: Production line
  • device: xgk-cpun: Specific PLC
  • environment: production: Deployment environment

2. PLC​

FieldDefaultMeaning
Transportfenetfenet = the binary protocol on TCP, to a FEnet module or a CPU's built-in Ethernet port. cnet-serial = a serial port on the MaestroHub host wired to a Cnet channel. cnet-tcp = Cnet over TCP, to a serial-to-Ethernet gateway or a FEnet module in XGT server mode
PLC Family(required, no default)XGK, XGB, XGI, XGR or XEC
Address(required for fenet and cnet-tcp)PLC, FEnet module or gateway host name or IP address, e.g. 192.168.1.30
Port2004TCP port, 1 to 65535. 2004 is FEnet's; a gateway serves Cnet on the port set on it
Station0Cnet only: the station number of the PLC's Cnet channel, 0 to 255, as set in XG5000
ChecksumonCnet only: send each request with its checksum and check the PLC's reply. Off sends the uppercase commands, which carry none
Bit Names on the WireflatXGK and XGB only: how a bit of a word device is named to the PLC. See Bit names on the wire
String Encodingutf-8How STRING values are stored in the PLC: utf-8, shift-jis or windows-1251
Connection Timeout5sMaximum time to reach the PLC and get its first answer (1s to 5m)
Response Timeout5sHow long one request waits for the PLC's reply (500ms to 1m)

Why PLC Family has no default. The family decides how an address is written and turned into LS's wire name, which devices exist and how large they are, the largest request, and the CPU byte of every FEnet header. A guessed family would be worse than a question, so you choose it.

Each function has its own Timeout (default 30m) that bounds the whole operation. Within it, each request waits at most the Response Timeout for its reply.

LS Electric XGT connection formLS Electric XGT connection form

The Connection tab: the transport, the PLC family and the PLC's address

3. Cnet on a Serial Line​

Choosing cnet-serial as the Transport replaces Address and Port with the serial line fields. They must match the settings of the PLC's Cnet channel.

FieldDefaultMeaning
Serial Device(required for cnet-serial)Serial port device path, e.g. /dev/ttyUSB0 or COM3
Baud Rate9600Line speed: 1200, 2400, 4800, 9600, 19200, 38400, 57600 or 115200, as set on the channel. The port uses eight data bits
ParityNN = none, E = even, O = odd, as set on the channel
Stop Bits11 or 2, as set on the channel
RS-485 ModeoffTurn on the serial driver's RS-485 transceiver mode (Linux); ignored on Windows

The serial device is opened on the host MaestroHub runs on, so the cable or USB adapter must be attached to that machine, and the device path must be one that host can open. Set the channel to eight data bits.

The connection is refused when it carries a setting it would ignore: a serial device with a TCP transport, an address with cnet-serial, or the word-and-hex-digit bit names on an XGI, XGR or XEC.

Setting up the PLC for Cnet​

A Cnet channel answers these commands only in the XGT server operating mode (LS's XGB Cnet manual, chapter 4). In XG5000, open the settings of the channel MaestroHub is wired to (a built-in Cnet channel of an XGB CPU, or a channel of a Cnet I/F module) and set:

  • the operating mode to XGT server,
  • the station number, which goes into Station,
  • the speed, data bits (eight), parity and stop bits, which go into the serial fields,

then write the parameters to the PLC. Many XGB CPUs have two built-in channels: channel 1 is RS-232C, one to one, and channel 2 is RS-485, up to 32 stations.

For Cnet over TCP, set up the channel behind the gateway the same way, and set the gateway's serial side to the same speed and framing. A FEnet module in XGT server mode also serves Cnet over TCP (FEnet module OS 6.0 or later).

Moving off the loader port​

Some older drivers read the PLC through the CPU's loader port, the RS-232C or USB port XG5000 connects to, often at the loader's 115200 baud. MaestroHub does not use it: LS does not publish its protocol, and nothing outside XG5000 documents or tests it, so a firmware change can break it without warning. Every PLC that has a loader port also has the documented protocols. To move:

  • On Ethernet: reach the PLC's FEnet module or built-in Ethernet port with the fenet transport. Nothing on the PLC changes.
  • On a serial line: move the cable from the loader port to a Cnet channel, set that channel to XGT server as above, and use the channel's speed and framing in MaestroHub, not the loader's 115200.

Bit names on the wire​

On an XGK or XGB, XG5000 names a bit of a word device by its word and one hex digit: M0172C is bit C of word M172. On the wire, LS's manuals give two forms for the same bit:

SettingM0172C goes out asSource
flat (default)%MX2764: the bit's number, 172 × 16 + 12LS's XGT FEnet manual (p.7-4) and XGB FEnet manual (p.5-5)
word-hex%MX172C: the word and the hex digitLS's XGB Cnet manual's example for U bits (p.7-5); one open-source library offers it for XGB bits that read wrong

MaestroHub follows LS's FEnet manuals by default. If a bit reads or writes the wrong place (for example M0172C changes a bit far from M172), switch the connection to word-hex and test again; then tell us which one your PLC took. The setting affects only the bits of P, M, K, L, F and U on XGK and XGB. Word devices are named the same either way, and an IEC address (%MX2764) is a bit number by definition, so the setting is not offered for XGI, XGR and XEC.

Testing the Connection​

Click Test Connection at the bottom of the form to try the current settings before saving. It connects as described in What happens on connect. Once the connection runs, its health probe makes the same round trip again and reports its time. When the PLC does not answer, the connection is closed and opened again.

Function Builder​

Creating LS Electric XGT Functions​

After the connection is saved:

  1. Open the connection and navigate to the Functions tab
  2. Click New Function to open the function type selection dialog
  3. Choose Read Device, Read Block or Write Device
  4. Fill the Basic tab (name, description, labels) and the Configuration tab (operation-specific parameters)
  5. Use the Test button to run the function against the live PLC before saving. Testing a Write Device function writes to the PLC
LS Electric XGT function typesLS Electric XGT function types

Two reads and one write

Devices​

Every function names its data by a device address, written as XG5000 shows it, in either letter case. A malformed address, or one the family has no such device for, is refused when the function is saved, with a message that names the family's devices.

XGK and XGB (letter devices):

DeviceWhat it isWritten asBITWordsWritable
PInput/output relayP00010, bit P0010AYesYesYes
MAuxiliary relayM00172, bit M0172CYesYesYes
KKeep relayK00010, bit K0010FYesYesYes
LLink relayL00010, bit L00103YesYesYes
FSpecial relay (system flags)F00010, bit F00100YesYesNo
TTimerT0005: as BIT its contact, as WORD its current valueYesYesYes
CCounterC0005: as BIT its contact, as WORD its current valueYesYesYes
USpecial module registerU01.02 (slot hex 01, word 02), bit U01.02.3YesYesYes
ZIndex registerZ00010NoYesYes
NCommunication data registerN00100NoYesNo
DData registerD00100NoYesYes
RFile registerR00100NoYesYes

The data type decides how a letter address is read: as BIT, a P, M, K, L, F or U address is its word number and one hex digit, 0 to F (M0172C is bit C of word 172); as any other type, the whole number is the word (M00172 is word 172). The device sizes are the larger CPU models' (an XGK's D runs to D524287); a PLC refuses an address beyond its own memory with "device area exceeded".

XGI, XGR and XEC (IEC addresses): % + the device + the size letter (X bit, B byte, W word, D double word, L long word) + the address.

DeviceWhat it isWritten asWritable
%I, %QInput and outputBase, slot and position: %IX0.0.3, %QW0.1.2Yes (%I as the PLC allows)
%MMemory%MW100, %MD50, %MX2764 (bit 2764 = word 172, bit 12)Yes
%R, %WFile registers%RW100, %WW100Yes
%K, %LPID and link flags%KW10, %LX100Yes
%UAnalog refresh flagsBase, slot and position: %UW0.3.7Yes
%ASymbolic and automatic variable area (XGI, XGR only)%AW100Yes
%F, %NSystem flags, P2P flags%FW0, %NW10No

The size letter of an IEC address must fit the data type: %MX for BIT, %MW for WORD and INT, %MW or %MD for DWORD, DINT and REAL, %MW, %MD or %ML for LREAL, %MB or %MW for STRING. A STRING is read from a linear device such as %M, not from one addressed by base and slot.

Data types:

Data TypeSizeA write takes
BITOne bittrue or false, 1 or 0, on or off
WORDOne wordA whole number, 0 to 65535
INTOne wordA whole number, -32768 to 32767
DWORDTwo words, low word firstA whole number, 0 to 4294967295
DINTTwo words, low word firstA whole number, -2147483648 to 2147483647
REALTwo words, low word firstA 32-bit floating-point number
LREALFour words, low word firstA 64-bit floating-point number
STRINGString Length bytesText that fits in String Length bytes, encoded with the connection's String Encoding. The text lies in the device's bytes in order, the first character in the low byte of the first word, and the rest is filled with zero bytes. This layout is not yet proven on a real PLC (see the Beta note at the top of this page)

Read Device (lsxgt.read.device)​

Purpose: Reads a typed value from one device, or Count consecutive values as a list, in one request.

ParameterDefaultMeaning
Device(required)A device address from the tables above
Data TypeWORDHow to interpret the value
Count11 to 1000. 1 returns the value; more returns a list. Not used for STRING
String Length1STRING only: the capacity in bytes, 1 to 256
Timeout30mBound on this operation (1s to 1h)

"The next value" is the next device of the data type's size: D00100 as DINT with Count 3 reads D100-D101, D102-D103 and D104-D105; M00100 as BIT with Count 4 reads bits M00100 to M00103. One request carries at most 1400 bytes of data on FEnet (700 words; 500 bytes on an XGB or XEC) and 60 words on Cnet. A longer run is refused before anything is sent, with a message that says to read fewer at a time.

Read Block (lsxgt.read.block)​

Purpose: Reads many named devices in the fewest requests, and returns every value by its name. Use it to read a machine's counts, setpoints and alarm bits in one node.

ParameterDefaultMeaning
Data Points(required)A list of points. Each point has a name, the key of its value in the result, a device, a data type (default WORD) and, for STRING, a length in bytes. Each name is used once
Timeout30mBound on this operation (1s to 1h)

Points of the same size are named together, up to sixteen devices to a request: all the bits in one request, the word devices in another. A value that takes several words (a DINT, an LREAL) takes that many places in the same request, so it is read whole. A STRING is read with a request of its own. When the PLC refuses a request that served several points, MaestroHub asks for each of those points on its own, so a device the PLC does not have does not take its neighbours with it.

A point that is not a device address is refused when the function is saved. A point the PLC refuses is reported by name in the result's errors, and the other points are still read. The node fails only when the link fails: when the connection drops, or when no point got any answer from the PLC.

Write Device (lsxgt.write.device)​

Purpose: Writes a typed value to one writable device, or a list of values to consecutive devices in one request.

ParameterDefaultMeaning
Device(required)A writable device: not F or N
Data TypeWORDHow to encode the value
Value(required)A value of the data type. A JSON list such as [1, 2, 3] writes consecutive devices in one request. Supports ((paramName)) templates
String Length1STRING only: the capacity in bytes; longer text is refused
Timeout30mBound on this operation (1s to 1h)
Write Device function parametersWrite Device function parameters

A Write Device function whose value is the ((setpoint)) parameter, filled by the pipeline

The write rules:

  • A bit is written as a bit. MaestroHub sends the bit itself, and the PLC sets or clears that bit only, so a bit its program changes in the same word in the meantime is never overwritten. MaestroHub never reads the word and writes it back. A list of bits ([true, false, true] to M00100) writes consecutive bits in one request, at most sixteen.
  • F and N cannot be written. LS lists the system flags and N for reading and monitoring only. Such a write is refused before anything is sent.
  • A list must fit in one request, so a write is carried out whole or not at all: at most 1400 bytes on FEnet (a little under 500 on an XGB or XEC, where the device's name shares the 512-byte request) and 58 or 59 words on Cnet (the device's name shares the 256-character frame). A STRING takes one text value per write.
  • Nothing is sent when a value does not fit its type: text into an INT, 70000 into a WORD, text longer than String Length.
A write happens when the node runs, or not at all

A write is never buffered for later delivery: a setpoint that arrives an hour late is a new decision, not the old one. A pipeline run started by a late (replayed) input does not execute the write unless the node allows late input. A write is sent once: when the PLC does not answer in time, it is not sent again by the connector, because the PLC may already have applied it. The node's Retry on Fail may send it again; writing the same value twice leaves the PLC in the same state. A write the PLC refused for its address or its data type is not retried.

Using Parameters​

The Value field supports ((parameterName)) placeholders; they appear in the Function Parameters block, where you set each one's type, whether it is required, and a default. For example, Value ((setpoint)) writes the node's setpoint parameter to the device the function names. The device itself is fixed when the function is saved, so the save can check it against the connection's family.

Pipeline Integration​

Use the functions you configure here as nodes inside the Pipeline Designer. Each function type has its own node:

  • LS Electric XGT Read Device (connected.lsxgt.read.device): executes a lsxgt.read.device function
  • LS Electric XGT Read Block (connected.lsxgt.read.block): executes a lsxgt.read.block function
  • LS Electric XGT Write Device (connected.lsxgt.write.device): executes a lsxgt.write.device function

These PLCs do not send data on their own: to poll one, drive the reads from a Schedule trigger.

LS Electric XGT node in the pipeline designerLS Electric XGT node in the pipeline designer

The Read Device node with its connection and function

For node-level details (output structure, execution settings), see the LS Electric XGT Nodes page.

For orchestration strategies that mix these PLCs with other data sources, see the Nodes page.

Common Use Cases​

Production counts and alarms to a historian or the UNS​

A Read Block of a machine's counts (D00100 as DINT), alarm bits (M0172C) and timer values (T0005 as WORD) on a Schedule trigger, routed to a historian or the Unified Namespace. Sixteen devices of one size share a request, so a block of related devices costs few round trips.

Many PLCs on one RS-485 line​

Several XGB CPUs on one RS-485 line, each with its own station number: one connection per line, with the functions of each PLC on it. The connection sends one request at a time, so the line is never shared by two requests.

Setpoints and recipes​

A parameterized Write Device function (Value: ((setpoint))) fed from an MES or an operator form, with a Condition node checking the range first. A list such as [120, 45, 3] writes a recipe to consecutive devices in one request.

Acknowledging alarms and setting control bits​

Write true to a bit (M0172C, %MX2764) to acknowledge an alarm or request a sequence. Only that bit changes; the program's other bits in the same word are left as they are.

Troubleshooting​

Error Reference​

The texts below leave out the lsxgt: that the messages start with. A refusal by the PLC ends with its code, for example (FEnet error 0x0004) or (Cnet NAK 7132).

What you seeMeaningRetried?
the PLC refused the request: device area exceeded: the address is beyond the PLC's memory (FEnet error 0x0004)The device is beyond the end of this PLC's memory (D99999 on a small CPU)No
the PLC refused the request: device area request error: the PLC has no such device (FEnet error 0x0003), or the PLC has no such device (Cnet NAK 1132)The PLC does not have that device: check PLC FamilyNo
the PLC refused the request: the address is beyond the device's area (Cnet NAK 7132)As FEnet error 0x0004, on CnetNo
the PLC refused the request: … data type …, address format errorThe PLC does not take the address or the size: check PLC Family and, for a bit, Bit Names on the WireNo
the PLC refused the request: the module has as many connections as it takes (FEnet error 0x0051)The FEnet module serves no more connectionsYes
the PLC refused the request: the FEnet module got no answer from the CPU, … dropped the request: its queue is fullThe module is busy or the CPU did not answer itYes
the PLC refused the request with … which LS's manual does not listA code LS's tables do not giveYes
no answer from the PLCThe request was sent and not answered within the Response Timeout. The connection is closed and opened againYes
the PLC's reply is damagedA reply whose checksum does not match, or a frame cut off: line noise on a serial lineYes
the reply does not answer the requestA reply with another invoke number, station or command: two masters on one line, or a wrong Station. The connection is closed and opened againYes
… cannot be written: F (special relay (system flags)) is read-only; LS lists it for reading and monitoring onlyA write to F or N. Nothing was sentNo
… (D) is a word device: LS gives it byte and word access only; read it as WORD and take the bit from the valueBIT on D, R, Z or NNo
an XGK has no device "X"; its devices are C D F K L M N P R T U ZA device letter the family does not have. Nothing was sentNo
%MW100 is an IEC address; an XGK takes devices as XG5000 shows them … (or the reverse)The address form of another family: check PLC FamilyNo
a DINT value starts at %MW or %MD, not at a bit (X) addressThe size letter of an IEC address does not fit the data typeNo
… values from D00000: …; read fewer at a timeThe run does not fit in one request. Nothing was sentNo
the ZR device is not supported …ZR has no documented wire name. On an XGB, use RNo
not connectedThe connection is not upYes, after reconnect

"Retried?" says whether the node's Retry on Fail setting sends the request again. A refusal that names the address or the data type, and a request MaestroHub refuses before sending, give the same answer every time, so they are not retried.

Connection Issues​

SymptomPossible CauseSolution
Test Connection fails with connect to the XGK at …Nothing answers at that address and port, or a firewall is in the wayCheck the PLC's IP address and that TCP port 2004 is reachable from the MaestroHub host
Test Connection fails with did not answer the FEnet status requestThe device took the TCP connection but did not answer a FEnet requestCheck that the address is the FEnet module or the CPU's Ethernet port, and the port 2004
Test Connection fails with did not answer a Cnet read of its system flagsNo answer on the Cnet channelCheck that the channel is set to XGT server in XG5000, that Station is the channel's station number, and that speed, parity and stop bits match. A PLC answers only its own station number
A Cnet connection fails with the PLC's reply is damagedLine noise, or the checksum setting differsKeep Checksum on, check the cable and its termination on RS-485
Bits read or write the wrong place on an XGK or XGBThe PLC takes the other bit-name formSwitch Bit Names on the Wire to word-hex and test again
Every request fails with the PLC has no such devicePLC Family does not match the PLCSet the family the PLC belongs to
A connection that worked through the loader port does not answerThe cable is on the loader portMove it to a Cnet channel set to XGT server, or use FEnet. See Moving off the loader port