Allen-Bradley PCCC Integration Guide
Read and write the data files of Allen-Bradley SLC 500, MicroLogix and PLC-5 controllers by address, over EtherNet/IP or a DF1 serial line.
- Status
- Beta
- Controllers
- SLC 500 · MicroLogix · PLC-5
- Transports
- EtherNet/IP (TCP 44818) · DF1 serial line
- Operations
- Read Address · Read Block · Write Address
- Triggers
- None: poll with a Schedule trigger
The SLC 500, MicroLogix and PLC-5 controllers keep their data in numbered data files and answer PCCC commands (Rockwell's "programmable controller communication commands"), not the tag services of ControlLogix. MaestroHub reads and writes these files by address, such as N7:0 or T4:0.ACC, over the controller's EtherNet/IP port or a DF1 serial line. This guide covers the connection, the address forms and what each one returns, the three function types, and how the matching nodes fit into the Pipeline Designer.
What stands behind the connector today:
- Its requests were answered correctly by three PLC simulators that other people wrote, each in its SLC 500, MicroLogix and PLC-5 modes. Wireshark's PCCC dissector decoded all 430 EtherNet/IP requests recorded in 42 of those sessions without complaint. libplctag's own client, which is proven on hardware, also reads and writes the test PLC that MaestroHub's own tests use.
- The file types each simulator covered:
- libplctag's
ab_server: integer, bit, float, long and string files, runs of elements, single bits changed by masked write, refusals (a missing file, a file of another type, an element past the end), and a block read in which one address does not exist. - A Python PLC simulator: timer, counter and control elements and their words, timer status bits, the status file, strings, longs, and an element numbered 255.
- A .NET PLC emulator with SLC 5/04, PLC-5/40E and MicroLogix 1400 memory, over EtherNet/IP and over a DF1 serial line with CRC and with BCC: integers, longs, strings, floats, bit writes and timer words. Its MicroLogix 1400 memory is a copy of a real controller's backup.
- libplctag's
What is not proven yet:
- It has not been run against a real controller of any family, nor over a real serial cable. The serial line was tested through a pseudo-terminal.
- ASCII (
A) files: no simulator has one. They are checked against MaestroHub's own test PLC only. - The byte order of floats and longs: simulators store the bytes they are sent. The order rests on Rockwell's DF1 manual and on libplctag's experience with hardware; for the PLC-5, whose floats keep the high word first, it also agrees with the .NET emulator's PLC-5 layout.
- The largest request each real model accepts is not known. MaestroHub puts at most 188 bytes of data in one request, which is within what Rockwell's manual gives for these controllers and what drivers proven on hardware send.
- The serial line's recovery (a message sent again after the controller rejects it, an enquiry after silence) is proven by MaestroHub's own scripted tests only.
Overview
The Allen-Bradley PCCC connector provides:
- Three controller families: SLC 500, MicroLogix and PLC-5, each with its own commands and byte order
- Data files: integer (
N), bit (B), float (F), long (L, MicroLogix only), string (ST), ASCII (A) and status (S) - Timers, counters and control: the preset, accumulated value, length and position words, and the status bits by name (
T4:0/DN), or the whole element as one object - Safe bit writes: a single bit is changed by the controller itself (a masked write), never read and written back
- Block reads: many named addresses in one node, merged into as few requests as fit
- Two transports: EtherNet/IP (TCP 44818), and a DF1 full-duplex serial line with CRC or BCC
Terms used in this guide
| Term | Meaning |
|---|---|
| PCCC | The command set of these controllers. One command reads or writes a run of values in one data file. |
| Data file | How these controllers hold data: numbered files of one type each. N7 is integer file 7, B3 a bit file, F8 a float file, T4 a timer file, ST9 a string file. |
| Element | One entry of a data file. N7:12 is element 12 of file N7. A timer, counter or control element has parts: two words and a set of status bits. |
| EtherNet/IP | The Ethernet transport of Rockwell devices, on TCP port 44818. The newer of these controllers take PCCC commands wrapped inside it. |
| DF1 | Rockwell's serial-line protocol for the same commands. MaestroHub uses DF1 full duplex: one controller on one serial line. |
| Masked write | A command that names the bits to change and their new values. The controller changes only those bits. |
Supported controllers
| PLC Family | Controllers | Over EtherNet/IP | Over a DF1 serial line |
|---|---|---|---|
slc500 | SLC 5/03, 5/04, 5/05 | An SLC 5/05's Ethernet port, or a 1761-NET-ENI in front of the controller's serial channel | A serial channel set to DF1 full duplex |
micrologix | MicroLogix 1000, 1100, 1200, 1400, 1500 | A MicroLogix with an Ethernet port, or a 1761-NET-ENI in front of its serial channel | A serial channel set to DF1 full duplex |
plc5 | PLC-5 | A PLC-5 with an Ethernet port that answers EtherNet/IP, or a 1761-NET-ENI in front of its serial channel | A serial channel set to DF1 full duplex |
MaestroHub sends each command to the device without opening a CIP connection (CIP is the request layer of EtherNet/IP). This is how libplctag and nodepccc reach these controllers, and a MicroLogix refuses some of the requests that open a CIP connection.
ControlLogix, CompactLogix and Micro800 controllers use tag names, not data files. Connect them with the EtherNet/IP connector instead.
Not supported
| What | Why |
|---|---|
Input and output image files (I:, O:) | Rockwell's manual and the drivers proven on hardware disagree on how these files are addressed, and no simulator can settle it. An I or O address is refused with that reason. |
BCD (D), message (MG), PID (PD), block transfer (BT), SFC status (SC) and programmable limit switch (PLS) files | Not supported in this version. An address with one of these letters is refused with a message that says so. |
| TCP port 2222 (CSP, an older Rockwell Ethernet wrapping used by PLC-5 Ethernet processors and the SLC 5/05) | Rockwell never published it, so there is no vendor source to build it from. A controller that answers only on port 2222 cannot be reached. |
| Routing through a ControlLogix chassis onto a DH+ or DH-485 network | Not in this version. |
| The half-duplex DF1 mode | Not in this version. The serial line is DF1 full duplex. |
| Listing the controller's data files | Not in this version. Take the addresses from the controller's program. |
| A read-group node | Not in this version. Read Block reads many named addresses in one node. |
| A trigger | These controllers do not send data on their own. Poll them with a Schedule trigger. |
What happens on connect
For EtherNet/IP, MaestroHub opens the TCP connection and an EtherNet/IP session. For a serial line, it opens the serial port. Then, on either transport, it reads the first word of the controller's status file. Any PCCC answer counts, also a refusal: it proves that a PCCC processor is listening. An open TCP port or serial port alone proves nothing, because a serial port opens whether or not anything is wired to it.
The connection sends one request at a time and matches every reply to its request by a transaction number. Use one MaestroHub connection per controller: these controllers serve a small, fixed number of connections, and a serial line serves one.
Connection Configuration
Creating an Allen-Bradley PCCC Connection
Navigate to Connections → New Connection → Allen-Bradley PCCC and fill in the form. It has four tabs: Connection, Functions, Scaling and Health. The Functions, Scaling and Health tabs unlock after the connection is saved.
1. Profile Information
| Field | Default | Description |
|---|---|---|
| Profile Name | - | A descriptive name for this connection profile (required). Must be unique across all connections. |
| Description | - | Optional description for this connection |
| Labels | - | Key-value pairs to categorize and organize the connection |
Example Labels
line: press-2: Production linedevice: slc-505: Specific controllerenvironment: production: Deployment environment
2. Controller
| Field | Default | Meaning |
|---|---|---|
| Transport | ethernetip | ethernetip = the controller's EtherNet/IP port, or a 1761-NET-ENI in front of a serial controller. serial = a serial port on the MaestroHub host wired to the controller's DF1 full-duplex channel |
| PLC Family | (required, no default) | slc500 = SLC 5/03, 5/04, 5/05. micrologix = MicroLogix 1000, 1100, 1200, 1400, 1500. plc5 = PLC-5 |
| Address | (required for ethernetip) | Controller host name or IP address, e.g. 192.168.1.20 |
| Port | 44818 | EtherNet/IP TCP port, 1 to 65535. 44818 is the standard port |
| Connection Timeout | 5s | Maximum time to reach the controller and get its first answer (1s to 5m) |
| Response Timeout | 5s | How long one request waits for the controller's reply (500ms to 1m) |
Why PLC Family has no default. The family decides which commands MaestroHub sends, how it encodes an address, and the order of the two words of a float. SLC 500 and MicroLogix controllers share one command set; long (L) files exist on MicroLogix only. The PLC-5 has its own commands and address form, and keeps a float's high word first. A guessed family would be worse than a question, so you choose it.
Each function has its own Timeout (default 30m) that bounds the whole operation. Within it, each request waits at most the Response Timeout for its reply.


The Connection tab: the transport, the PLC family and the controller's address
3. Serial Line (DF1)
Choosing serial as the Transport replaces Address and Port with the serial line fields. They must match the settings of the controller's serial channel.
| Field | Default | Meaning |
|---|---|---|
| Serial Device | (required for serial) | Serial port device path, e.g. /dev/ttyUSB0 or COM3 |
| Baud Rate | 19200 | Line speed: 1200, 2400, 4800, 9600, 19200, 38400, 57600 or 115200, as set on the controller's channel. A DF1 link always uses eight data bits |
| Parity | N | N = none, E = even, O = odd, as set on the controller's channel |
| Stop Bits | 1 | 1 or 2 |
| Error Check | crc | How each DF1 message is checked: crc or bcc. It is the Error Detection setting of the controller's channel, and both ends must use the same one |
| Station Address | 0 | The DF1 node address MaestroHub sends from, 0 to 254 |
| PLC Node Address | 1 | The DF1 node address of the controller's channel, 0 to 254 |
The serial device is opened on the host MaestroHub runs on, so the cable or USB adapter must be attached to that machine, and the device path must be one that host can open. The channel must be set to DF1 full duplex; the half-duplex mode is not supported.
MaestroHub waits one second for the controller to acknowledge a message, then asks it to repeat its answer, up to three times. A message the controller rejects is sent again, up to three times. These are the values a controller's own DF1 channel starts with; they are not settings.
The connection is refused when it carries a setting it would ignore: a serial device with the ethernetip transport, or an address with the serial transport.
Testing the Connection
Click Test Connection at the bottom of the form to try the current settings before saving. It connects as described in What happens on connect. Once the connection runs, its health probe reads the first word of the status file again and reports the round trip. When the controller does not answer, the connection is closed and opened again.
Function Builder
Creating Allen-Bradley PCCC Functions
After the connection is saved:
- Open the connection and navigate to the Functions tab
- Click New Function to open the function type selection dialog
- Choose Read Address, Read Block or Write Address
- Fill the Basic tab (name, description, labels) and the Configuration tab (operation-specific parameters)
- Use the Test button to run the function against the live controller before saving. Testing a Write Address function writes to the controller


Two reads and one write
Addresses
Every function names its data by address, written as RSLogix writes it, in either letter case. The file letter fixes the data type, so there is no data type to choose.
| Address | What it names | A read returns | Can be written |
|---|---|---|---|
N7:0 | Element 0 of integer file 7 | A whole number, -32768 to 32767 | Yes |
N7:0/3 | Bit 3 of that element | true or false | Yes, by masked write |
B3:0 | Word 0 of bit file 3 | The 16 bits as a number, 0 to 65535 | Yes |
B3:0/5 | Bit 5 of word 0 | true or false | Yes, by masked write |
B3/21 | Bit 21 of the file, counted from its start (the same bit as B3:1/5) | true or false | Yes, by masked write |
F8:1 | Element 1 of float file 8 | A 32-bit floating-point number | Yes |
L20:0 | Element 0 of long file 20 (MicroLogix only) | A whole number, 32-bit | Yes |
L20:0/31 | Bit 31 of that long (bits 0 to 31) | true or false | No: write the whole long |
ST9:0 | Element 0 of string file 9 | Text, up to 82 characters | Yes |
A12:0 | Element 0 of ASCII file 12 | Text: the element's two characters | Yes |
S:1 | Word 1 of the status file (S is file 2, so S2:1 is the same) | The 16 bits as a number, 0 to 65535 | Yes |
S:1/5 | Bit 5 of that word | true or false | Yes, by masked write |
T4:0 | The whole timer element | An object: {"PRE": 100, "ACC": 5, "EN": true, "TT": true, "DN": false} | No: write one of its parts |
T4:0.PRE, T4:0.ACC | The timer's preset and accumulated value | A whole number, -32768 to 32767 | Yes |
T4:0/EN, /TT, /DN | The timer's status bits | true or false | No |
C5:0 | The whole counter element | An object with PRE, ACC and the status bits | No: write one of its parts |
C5:0.PRE, C5:0.ACC | The counter's preset and accumulated value | A whole number, -32768 to 32767 | Yes |
C5:0/CU, /CD, /DN, /OV, /UN, /UA | The counter's status bits | true or false | No |
R6:0 | The whole control element | An object with LEN, POS and the status bits | No: write one of its parts |
R6:0.LEN, R6:0.POS | The control element's length and position | A whole number, -32768 to 32767 | Yes |
R6:0/EN, /EU, /DN, /EM, /ER, /UL, /IN, /FD | The control element's status bits | true or false | No |
- A status bit of a timer, counter or control element can also be written as
T4:0.DN, or by its number,T4:0/13. All three name the same bit. - On an SLC 500 or MicroLogix, file numbers and element numbers run from 0 to 255. On a PLC-5 they run from 0 to 999. An address outside that range is refused before anything is sent.
- A long (
L) address on an SLC 500 or PLC-5 connection is refused before anything is sent. - Results give the address back in one standard form:
b3/21comes back asB3:1/5,S:1/5asS2:1/5andT4:0/13asT4:0/DN. - Which files and elements exist is up to the controller's program. An address the program does not have is refused by the controller; see Troubleshooting.
Values, by file type:
| File | What a write takes |
|---|---|
Integer (N); preset, accumulated, length and position words | A whole number, -32768 to 32767 |
Bit (B), status (S) | A whole number, 0 to 65535. A negative number down to -32768 is taken as the same 16 bits, so a value read from an integer file can be written back |
Long (L) | A whole number, -2147483648 to 2147483647 |
Float (F) | A finite number within the range of a 32-bit float, stored as the nearest 32-bit floating-point number |
String (ST) | Text of up to 82 characters, one byte per character (ISO 8859-1). A character beyond that set is refused |
ASCII (A) | Text of up to two characters. A single character is padded with a space |
| A bit | true or false, 1 or 0, on or off |
Read Address (pccc.read)
Purpose: Reads the value at one address, or Count consecutive values as a list.
| Parameter | Default | Meaning |
|---|---|---|
| Address | (required) | A data-file address from the table above. It can be a ((parameter)) or contain one (N7:((element))): the filled-in address is checked when the function runs, and nothing is sent when it is not an address |
| Count | 1 | 1 to 1000. 1 returns the value; more returns a list |
| Timeout | 30m | Bound on this operation (1s to 1h) |
What "the next value" is depends on the address:
- An element (
N7:0,F8:1,ST9:0): the next elements. - A part or status bit of a timer, counter or control (
T4:0.ACC,T4:0/DN): the same part of the next elements.T4:0.ACCwith Count 3 gives the accumulated values ofT4:0,T4:1andT4:2. - A bit of a word (
B3:0/14): the next bits, carrying on into the next word.B3:0/14with Count 4 givesB3:0/14,B3:0/15,B3:1/0andB3:1/1. - A whole timer, counter or control (
T4:0): the next whole elements, each as an object.
One request carries at most 188 bytes of data: 94 integer, bit, status or ASCII elements, 47 floats or longs, 31 timers, counters or control elements, or 2 strings. A longer read is sent as several requests, one after the other. A read that would run past the end of the file range of the family is refused before anything is sent.
Read Block (pccc.read.block)
Purpose: Reads many named addresses in the fewest requests, and returns every value by its name. Use it to read a machine's counts, setpoints and alarm bits in one node.
| Parameter | Default | Meaning |
|---|---|---|
| Data Points | (required) | A list of points. Each point has a name, the key of its value in the result, and an address such as N7:0, B3:0/5 or T4:0.ACC. Each name is used once. A point without a name is named by its address |
| Timeout | 30m | Bound on this operation (1s to 1h) |
Each point reads one value. Points in the same data file are read together, with the elements between them, when they fit in one request. When the controller refuses a request that served several points, MaestroHub asks for each of those points on its own, so an address that does not exist does not take its neighbours with it.
A point that is not an address is refused when the function is saved. A point the controller refuses, or one the family cannot hold (a long file on an SLC 500), is reported by name in the result's errors, and the other points are still read. The node fails only when the link fails: when the connection drops, or when no point got any answer from the controller.
Write Address (pccc.write)
Purpose: Writes one value to an address, or a list of values to consecutive elements in one request.
| Parameter | Default | Meaning |
|---|---|---|
| Address | (required) | A writable address: an element (N7:10, F8:2, ST9:0), a bit of a word (B3:0/5, N7:0/3), or the preset, accumulated value, length or position of a timer, counter or control (T4:0.PRE, C5:0.ACC, R6:0.POS). It can be a ((parameter)) or contain one |
| Value | (required) | A number, true or false for a bit, or text for a string. A JSON list such as [1, 2, 3] writes consecutive elements, or consecutive bits of one word. Supports ((paramName)) templates |
| Timeout | 30m | Bound on this operation (1s to 1h) |


A Write Address function whose element and value are the ((element)) and ((setpoint)) parameters, filled by the pipeline
The write rules:
- A bit is changed by the controller. MaestroHub sends a masked write: the bits to change and their new values. The controller changes those bits itself, so a bit its program changes in the same word in the meantime is never overwritten. MaestroHub never reads the word and writes it back. A list of bits (
[true, false, true]toB3:0/4) changes consecutive bits of the same word in one masked write; it may not run past bit 15. - Status bits cannot be written.
T4:0/DN,C5:0/CU,R6:0/ENand the other status bits of timers, counters and control are set by the controller's program on every scan. Write the preset, accumulated value, length or position instead. A whole element (T4:0) cannot be written either: write one of its parts. - A bit of a long cannot be written. The controller changes single bits in 16-bit words only. Write the whole long (
L20:0) instead. Reading a bit of a long works. - A list must fit in one request, so a write is carried out whole or not at all: at most 94 integer, bit or status elements, or 47 floats or longs. A string or ASCII element takes one text value per write. A preset, accumulated, length or position word takes one value.
- Nothing is sent when a value does not fit its address: text into an integer,
70000intoN7, an address that is no address, a status bit.
A write is never buffered for later delivery: a setpoint that arrives an hour late is a new decision, not the old one. A pipeline run started by a late (replayed) input does not execute the write unless the node allows late input. A write that got no answer may be sent again by the node's Retry on Fail: writing the same value twice leaves the controller in the same state. A write the controller refused for its address, its command or a protection is not retried.
Using Parameters
The Address and Value fields support ((parameterName)) placeholders; they appear in the Function Parameters block, where you set each one's type, whether it is required, and a default. For example, Address N7:((element)) and Value ((setpoint)) write the node's setpoint parameter to the integer element the element parameter names.
Pipeline Integration
Use the functions you configure here as nodes inside the Pipeline Designer. Each function type has its own node:
- Allen-Bradley PCCC Read Address (
connected.pccc.read): executes apccc.readfunction - Allen-Bradley PCCC Read Block (
connected.pccc.read.block): executes apccc.read.blockfunction - Allen-Bradley PCCC Write Address (
connected.pccc.write): executes apccc.writefunction
These controllers do not send data on their own: to poll one, drive the reads from a Schedule trigger.


The Read Address node with its connection and function
For node-level details (output structure, execution settings), see the Allen-Bradley PCCC Nodes page.
For orchestration strategies that mix these controllers with other data sources, see the Nodes page.
Common Use Cases
Production counts and alarms to a historian or the UNS
A Read Block of a machine's counts (N7:0), alarm bits (B3:0/5) and timer values (T4:0.ACC) on a Schedule trigger, routed to a historian or the Unified Namespace. Points in the same file share a request, so a block of related addresses costs few round trips.
Watching a timer or counter
Read a whole timer (T4:0) or counter (C5:0) to get its preset, accumulated value and status bits in one value, for example to see when a cycle timer is done (DN) or a counter has overflowed (OV).
Setpoints and recipes
A parameterized Write Address function (Value: ((setpoint))) fed from an MES or an operator form, with a Condition node checking the range first. A list such as [120, 45, 3] writes a recipe to consecutive elements in one request.
Acknowledging alarms and setting control bits
Write true to a bit (B3:0/5) to acknowledge an alarm or request a sequence. Only that bit changes; the program's other bits in the same word are left as they are.
Troubleshooting
Error Reference
The texts below leave out the pccc: that most messages start with. A refusal by the controller ends with its status codes, for example (status 0xF0, extended status 0x06).
| What you see | Meaning | Retried? |
|---|---|---|
the PLC refused the request: illegal command or format: the PLC does not understand this command; check the PLC family of the connection | The controller does not take the commands of the chosen family | No |
the PLC refused the request: the command cannot be executed: the PLC does not carry out this command; check the PLC family of the connection | Same: the family does not match the controller | No |
the PLC refused the request: the address does not point to something usable: the file or the element does not exist in the PLC, or the file is of another type than the address says | The file or element is not in the controller's program, or the file letter does not match the file (B7:0 where file 7 is an integer file) | No |
the PLC refused the request: addressing problem, or the memory is protected: the file or the element does not exist in the PLC, or the memory is protected against writes | The file or element does not exist, or the memory is write-protected | No |
the PLC refused the request: illegal data type: the file is of another type than the address says | The file letter does not match the file's type | No |
the PLC refused the request: the file is the wrong size: the file is shorter than the request needs | The element, or the last of Count values, is past the end of the file | No |
… run past the end of the file | The run of values goes beyond element 255 (999 on a PLC-5). Nothing was sent | No |
long (L) files exist on MicroLogix controllers only, and this connection is to a … | A long address on an SLC 500 or PLC-5 connection. Nothing was sent | No |
the PLC refused the request: the processor is in Program mode | The controller is in Program mode | Yes |
the PLC refused the request: access denied: improper privilege: the file or the processor is protected against this access | The file or the processor is protected | No |
… does not support the Execute PCCC service: it does not take PCCC commands this way (CIP status 0x08). A ControlLogix or CompactLogix is reached with the EtherNet/IP connector instead (or has no PCCC object, CIP status 0x05) | The device answers EtherNet/IP but passes no command to a PCCC processor | No |
no answer from the device: … | EtherNet/IP: the request was sent and not answered within the Response Timeout. The connection is closed and opened again | Yes |
no answer from the PLC on the serial line: it did not acknowledge the message; check the cable, the baud rate, the parity and that the PLC's channel is set to DF1 full duplex | Nothing on the serial line acknowledged the message | Yes |
the PLC rejected the message 4 times; check that both ends use the same error check (CRC or BCC), baud rate and parity | The controller answered every copy of the message with "rejected". The line stays usable | Yes |
no answer from the PLC on the serial line: it acknowledged the request and sent no reply | The controller took the message and sent no answer within the Response Timeout | Yes |
… cannot be written: the status bits of a timer are set by the PLC's program | A write to a status bit (also of a counter or control). Nothing was sent | No |
… cannot be written: the PLC changes single bits in 16-bit words only; write the whole long instead | A write to a bit of a long. Nothing was sent | No |
… one write carries at most 94 integer elements | The list does not fit in one request. Nothing was sent | No |
70000 is outside -32768..32767 (N7:10) | The value does not fit the element. Nothing was sent | No |
address "O:0": output files are not supported: … | An address of a file type that is not supported. Nothing was sent | No |
not connected | The connection is not up | Yes, after reconnect |
"Retried?" says whether the node's Retry on Fail setting sends the request again. A refusal that names the address, the command or a protection, and a request MaestroHub refuses before sending, give the same answer every time, so they are not retried.
Connection Issues
| Symptom | Possible Cause | Solution |
|---|---|---|
Test Connection fails with connect to the … at … | Nothing answers at that address and port, or a firewall is in the way | Check the controller's IP address and that TCP port 44818 is reachable from the MaestroHub host |
Test Connection fails with did not answer a read of its status file | The device took the connection but did not answer a PCCC read | Check that the address is the controller or its 1761-NET-ENI. A controller that answers only on port 2222 (CSP) cannot be reached |
| The error names CIP status 0x05 or 0x08 | The device is not a PCCC processor, for example a ControlLogix or CompactLogix | Use the EtherNet/IP connector for Logix and Micro800 controllers |
Every request fails with check the PLC family of the connection | PLC Family does not match the controller | Set the family the controller belongs to |
A serial connection fails with rejected the message | Error Check, Baud Rate or Parity differ from the controller's channel | Set them as the channel is set; the error check is the channel's Error Detection setting |
A serial connection fails with did not acknowledge the message | No cable, a wrong device path, a wrong baud rate or parity, the channel is not in DF1 full duplex, or PLC Node Address is not the channel's node address (a message for another node gets no answer at all) | Check the cable and the device path, match the channel's settings, set the channel to DF1 full duplex, and set PLC Node Address to the channel's node address |
A serial connection fails with acknowledged the request and sent no reply | The controller took the message, but its reply did not arrive within the Response Timeout | Raise Response Timeout on a slow line; if it keeps happening, check the line for noise |
Requests fail with the processor is in Program mode | The controller is in Program mode | Switch the controller to Run. The failure is transient, so a retry succeeds once it runs |